Chart

Wire Size by Distance Chart

Smallest copper wire for 15, 20 and 30 A circuits over 25 to 300 ft on 120 V and 240 V, sized for a 3 % voltage drop, with the formula and a worked example.

Updated 2026-11-23

ElectricalFree, no sign-upWorked examples

How thick the wire needs to be depends on how far it runs. A long run loses voltage, and the load gets less than the supply provides. These charts give the smallest copper wire for a 3 % voltage drop at 25 to 300 feet, for 15, 20 and 30 A circuits on 120 V and 240 V. Each answer is also checked against the smallest wire the NEC allows for that breaker size, so a short run never returns a wire that is too small for the breaker.

Smallest copper AWG for a 3 % drop, 120 V single-phase, conductors at 75 °C
One-way run15 A20 A30 A
25 ft141210
50 ft12108
75 ft1088
100 ft886
150 ft864
200 ft643
300 ft432
Smallest copper AWG for a 3 % drop, 240 V single-phase, conductors at 75 °C
One-way run15 A20 A30 A
25 ft141210
50 ft141210
75 ft141210
100 ft12108
150 ft1088
200 ft886
300 ft864

Run length is one-way, from the panel to the load. The return conductor is counted for you.

How the sizes are chosen

Vdrop = 2 × I × L × ρ / A ≤ 0.03 × V

For each current and length, the chart takes the smallest AWG whose drop is within 3 % of the supply voltage, with copper at 75 °C and resistance only. It then applies a floor: 14 AWG for a 15 A circuit, 12 AWG for 20 A and 10 AWG for 30 A, the smallest copper conductors the NEC allows to be protected by those devices (240.4(D)). The calculation is the same one behind the voltage drop chart and the voltage drop calculator.

Worked example

A 20 A load sits 150 ft from the panel on a 240 V circuit. The 240 V chart gives 8 AWG. Check it: 8 AWG drops 0.153 V per amp per 100 ft, so 0.153 × 20 × 1.5 = 4.6 V, which is 1.9 % of 240 V. The next size down, 10 AWG, would drop 7.3 V, or 3.04 %, just over the limit.

On a 120 V circuit the same load needs 6 AWG. 8 AWG would drop 4.6 V, which is 3.8 % of 120 V. Using 240 V halves the current for the same power, and the wire gets smaller.

On a short run the floor takes over. A 20 A load 25 ft away would pass the drop test with 14 AWG at 2.6 % on 120 V, but the chart says 12 AWG, because 14 AWG may not be protected by a 20 A breaker.

What this chart does not check

The NEC does not set a mandatory voltage drop limit for ordinary circuits. It recommends 3 % for a branch circuit and 5 % for feeder and branch together. The details are in the NEC voltage drop guide.

Questions

What size wire for 100 feet at 20 amps?

10 AWG copper on a 240 V circuit, and 8 AWG on 120 V, for a 3 % drop.

What size wire for 200 feet at 30 amps on 240 V?

6 AWG copper. On 120 V it is 3 AWG.

Why does the chart stop at 30 amps?

Above 30 A the wire is chosen by its current rating first, and that depends on temperature, insulation and installation, so a distance chart alone could give a wire that is too small. The wire size calculator handles that case.

Is 3 % the right limit?

It is the NEC recommendation for a branch circuit, not a requirement. A looser limit may be acceptable for a load that tolerates it, and a tighter one is better for motors and sensitive equipment.

Wire size by distance — extended reference

AWG needed for 3% drop at 240 V, copper at 75°C, common circuit sizes:

Distance (one-way) 15 A circuit 20 A circuit 30 A circuit 50 A circuit
25 ft 14 AWG 12 AWG 10 AWG 8 AWG
50 ft 14 AWG 12 AWG 10 AWG 6 AWG
75 ft 14 AWG 12 AWG 10 AWG 6 AWG
100 ft 12 AWG 10 AWG 8 AWG 4 AWG
150 ft 10 AWG 8 AWG 6 AWG 3 AWG
200 ft 8 AWG 8 AWG 6 AWG 2 AWG
250 ft 8 AWG 6 AWG 4 AWG 1 AWG
300 ft 6 AWG 6 AWG 4 AWG 1/0 AWG

For 120 V circuits, the same run length needs wire two AWG sizes larger (one size larger for 30 A). Use this table for planning; verify with the calculator for the exact circuit.

Why 240 V circuits use smaller wire than 120 V

At 240 V, the same wattage requires half the current. Lower current means lower voltage drop for the same wire, so a smaller wire satisfies the 3% limit. This is the main cost benefit of 240 V branch circuits for high-draw loads such as EV chargers and dryers:

Load (watts) 120 V current 240 V current 240 V wire at 100 ft
1,800 W 15 A 7.5 A 12 AWG
3,600 W 30 A 15 A 10 AWG
7,200 W (EV charger) 60 A (not on 120 V) 30 A 8 AWG
9,600 W (range) — 40 A 6 AWG

Derating factors that may require a larger wire

The chart assumes free-air or standard conduit at 30°C with no more than three current-carrying conductors. These conditions require a larger wire:

Condition NEC correction Practical effect
Ambient > 30°C Table 310.15(B)(1)(a) Up to 2 AWG sizes larger in attics
> 3 conductors in conduit Table 310.15(C)(1) 4 conductors: 80% of ampacity
Continuous load (3 h+) 210.20(A) × 1.25 Effectively raises required ampacity
60°C terminals (older gear) 110.14(C) Use 60°C column even with 90°C cable

A 20 A circuit in a hot attic conduit with 6 conductors may need 8 AWG instead of 12 AWG for ampacity, regardless of the voltage drop calculation. Always check ampacity and derating separately from drop.

NEC minimum wire sizes per breaker

Regardless of run length or voltage drop, NEC 240.4(D) sets absolute minimums for copper:

Breaker size Minimum copper wire
15 A 14 AWG
20 A 12 AWG
30 A 10 AWG
40 A 8 AWG
60 A 6 AWG

The chart already enforces these floors. A 25 ft, 20 A circuit at 240 V passes the drop test with 14 AWG, but the chart returns 12 AWG because NEC 240.4(D) prohibits 14 AWG on a 20 A breaker.

More Q&As

What size wire for a 20 A, 50 ft run at 240 V?

12 AWG. The drop on 12 AWG: 0.386 V/A/100 ft × 20 A × 0.5 = 3.86 V = 1.6% of 240 V. Well within 3%. The NEC floor for a 20 A circuit is also 12 AWG, so no larger wire is needed.

Does the 3% rule apply to low-voltage DC circuits?

Not under the NEC, which does not mandate a specific drop limit for most circuits. For solar PV, NEC 690.8 guidance suggests 1-2% drop for array wiring. For 12 V and 48 V battery systems, designers typically use 1-3% because low-voltage drop wastes stored energy directly as heat in the wire.

My wire must pass through an attic where summer temperatures hit 55°C. What derating applies?

From NEC Table 310.15(B)(1)(a), at 55°C the correction factor for 90°C-rated cable (THHN) is 0.76. A 20 A circuit needs 20 A × 1.25 (continuous) × (1 / 0.76) = 32.9 A of tabulated ampacity. 10 AWG THHN at 90°C = 40 A. The drop check with 10 AWG at that run length is then secondary.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.