This chart lists the diameter, cross-sectional area and DC resistance of AWG conductors. Resistance is given for copper and aluminum at 20 °C and at 75 °C, a common conductor rating. The values are calculated for a solid round conductor from the AWG definition and the resistivity of each metal.
| AWG | Diameter (mm) | Area (mm²) | Cu 20 °C | Cu 75 °C | Al 20 °C | Al 75 °C |
|---|---|---|---|---|---|---|
| 4/0 | 11.684 | 107.22 | 0.0490 | 0.0596 | 0.0803 | 0.0982 |
| 3/0 | 10.405 | 85.03 | 0.0618 | 0.0752 | 0.1013 | 0.1238 |
| 2/0 | 9.266 | 67.43 | 0.0779 | 0.0948 | 0.1278 | 0.1561 |
| 1/0 | 8.251 | 53.48 | 0.0983 | 0.1195 | 0.1611 | 0.1968 |
| 1 | 7.348 | 42.41 | 0.1239 | 0.1507 | 0.2031 | 0.2482 |
| 2 | 6.544 | 33.63 | 0.1563 | 0.1900 | 0.2562 | 0.3129 |
| 3 | 5.827 | 26.67 | 0.1970 | 0.2396 | 0.3230 | 0.3946 |
| 4 | 5.189 | 21.15 | 0.2485 | 0.3022 | 0.4073 | 0.4976 |
| 6 | 4.115 | 13.30 | 0.3951 | 0.4805 | 0.6476 | 0.7912 |
| 8 | 3.264 | 8.37 | 0.6282 | 0.7640 | 1.0298 | 1.2581 |
| 10 | 2.588 | 5.261 | 0.999 | 1.215 | 1.637 | 2.000 |
| 12 | 2.053 | 3.309 | 1.588 | 1.932 | 2.604 | 3.181 |
| 14 | 1.628 | 2.081 | 2.525 | 3.071 | 4.140 | 5.058 |
| 16 | 1.291 | 1.309 | 4.015 | 4.883 | 6.583 | 8.042 |
| 18 | 1.024 | 0.823 | 6.385 | 7.765 | 10.467 | 12.787 |
| 20 | 0.812 | 0.518 | 10.152 | 12.347 | 16.643 | 20.332 |
| 22 | 0.644 | 0.326 | 16.143 | 19.632 | 26.464 | 32.330 |
| 24 | 0.511 | 0.205 | 25.668 | 31.216 | 42.079 | 51.406 |
How it is calculated
R = ρ × L / A, with ρ(T) = ρ20 × (1 + α × (T − 20))
The AWG number n gives the diameter d, and the area is π d² / 4. The resistivity ρ at 20 °C is 0.017241 Ω·mm²/m for copper and 0.028264 for aluminum. The temperature coefficient α is 0.00393 per °C for copper and 0.00403 for aluminum. The AWG to mm² converter gives the diameter and area for any gauge.
Worked example
A 14 AWG copper cable runs 200 ft to a load, so the loop is 400 ft of conductor. At 20 °C the resistance is 2.525 Ω per 1,000 ft × 0.4 = 1.01 Ω. At 10 A that loses 10.1 V, which is 8.4 % of a 120 V supply. With the conductor at 75 °C the resistance rises to 3.071 × 0.4 = 1.23 Ω and the drop to 12.3 V. Moving to 10 AWG (0.999 Ω per 1,000 ft at 20 °C) cuts the loss to 4.0 V.
Differences from published tables
- Stranding. Stranded conductors are a few percent higher in resistance than solid ones of the same size, because the individual wires follow a slightly longer path. Code and manufacturer tables for stranded wire give the higher figure. Use those for a final design.
- Coating. Tinned or coated copper has slightly higher resistance than bare.
- AC resistance. At 60 Hz, large conductors have a small skin effect, and reactance adds to the impedance. For long, large conductors use an impedance table.
Using it
Resistance is the starting point for voltage drop, power loss and fault current. Power lost in a conductor is I² × R, so a 10 A load through 1.01 Ω wastes 101 W as heat. The voltage drop chart turns these resistances into volts per amp and maximum lengths.
Questions
What is the resistance of 12 AWG copper wire?
1.588 Ω per 1,000 ft at 20 °C, or 1.932 Ω at 75 °C, for a solid conductor.
Why does resistance go up as the AWG number goes down?
A smaller AWG number is a thicker wire with more area, so its resistance is lower. The numbers run backwards: 4/0 is the thickest and 24 the thinnest on this chart.
How does temperature change the resistance?
Copper rises by about 0.4 % per °C. From 20 °C to 75 °C that is about 22 %.
How do I find the total resistance of a circuit loop?
Add the resistance of the outgoing conductor and the return conductor. For a 100 ft run with 12 AWG copper, the loop is 200 ft. At 20 °C: 1.588 × 0.2 = 0.318 Ω. Apply Ohm’s law to get the voltage drop.
Is aluminum resistance close enough to substitute for copper?
No. Aluminum has about 1.64 times the resistance of copper for the same AWG. A 2 AWG aluminum cable has roughly the same resistance as a 4 AWG copper cable. Aluminum is used in feeders for cost and weight, but the cable must be sized up accordingly.
Voltage drop from resistance
Voltage drop is the most direct use of the chart. The formula is:
where I is the current in amps and Rloop is the total resistance of the outgoing and return conductors. For a 50 A load through 150 ft of 6 AWG copper (loop = 300 ft), the resistance at 20 °C is 0.395 × 0.3 = 0.1185 Ω. Voltage drop is 50 × 0.1185 = 5.9 V on a 240 V circuit, or 2.5 %. The NEC recommends not exceeding 3 % on branch circuits (5 % to the final load including feeders). The voltage drop calculator handles arbitrary lengths and conductor types in one step.
Power loss
The same resistance causes heat. Power dissipated in the conductors is:
For the 50 A, 6 AWG example above, that is 50² × 0.1185 = 296 W lost in the cable run. At typical electricity rates, running a 50 A circuit continuously for a year costs roughly 260 kWh just in cable heat. This is why upsizing conductors on long, heavily loaded runs has a real payback.
Copper versus aluminum — practical comparison
| AWG | Cu R (Ω/1,000 ft, 20 °C) | Al R (Ω/1,000 ft, 20 °C) | Al:Cu ratio |
|---|---|---|---|
| 1/0 | 0.0983 | 0.161 | 1.64 |
| 2/0 | 0.0779 | 0.128 | 1.64 |
| 3/0 | 0.0618 | 0.101 | 1.63 |
| 4/0 | 0.0490 | 0.0804 | 1.64 |
| 350 kcmil | 0.0297 | 0.0486 | 1.64 |
Aluminum feeders save cost and weight on long runs, but the connection is more critical. Aluminum oxidizes rapidly and connections must use approved anti-oxidant compound with approved connectors. Aluminum is not permitted in sizes below 8 AWG under most code interpretations for branch circuits.
NEC ampacity and resistance — the two separate limits
A conductor must meet two criteria:
- Ampacity (NEC Table 310.12): the maximum continuous current the insulation can handle at a given ambient temperature.
- Voltage drop: not a code requirement on most circuits, but a performance issue. The NEC only recommends 3 % on branch circuits and 5 % total to the utilization equipment.
A 10 AWG copper conductor in conduit has a 75 °C ampacity of 35 A. It may also carry 50 A momentarily, but its voltage drop will be higher, and its temperature will exceed the rating. Sizing from ampacity alone without checking voltage drop is a common error on long runs.
Temperature derating
Resistance in this chart is at 20 °C (68 °F), the standard reference. The table also gives 75 °C values, which are closer to actual operating conditions. For intermediate temperatures, the linear formula applies:
For aluminum, substitute α = 0.00403.
Ampacity also derates with ambient temperature. If the air around a conduit is 40 °C rather than the standard 30 °C, NEC Table 310.15(B)(1) applies a correction factor. At 40 °C ambient the factor is 0.91 on 75 °C conductors. A 35 A conductor is derated to 32 A. This is separate from the resistance increase — the derating protects the insulation, not just the resistance calculation.
Fault current and cable impedance
On short circuits, the resistance of the circuit conductors limits the available fault current. A large transformer may supply 20 kA at its terminals, but 30 m of 4 AWG copper (loop resistance about 0.012 Ω at 75 °C) limits the fault current at the far end to roughly 20,000 / (1 + 0.012 × 20,000 / 480) ≈ 10 kA. This is why protective devices must be rated for the current at their location, not just at the transformer, and why the cable end fault current calculator is a useful check after the transformer chart.