Guide

NEC Voltage Drop: What the 3 % and 5 % Mean

What the NEC says about voltage drop: 3% on a branch circuit, 5% combined. Why it's a recommendation, not a requirement, with worked examples in AWG.

Updated 2026-11-15

ElectricalFree, no sign-upWorked examples

Most voltage drop questions in US work come down to two numbers, 3 % and 5 %, and one question: are they required? Mostly they are not. This guide explains where the numbers come from, how they are applied, and how to size wire for them in AWG, with examples you can check by hand.

Short answer. The NEC recommends no more than 3 % voltage drop on a branch circuit or feeder and 5 % from the service to the farthest outlet. These figures sit in informational notes, so they are not enforceable unless your specification or local authority adopts them.

System voltage 3 % drop 5 % drop
120 V 3.6 V 6.0 V
208 V 6.24 V 10.4 V
240 V 7.2 V 12.0 V
277 V 8.31 V 13.85 V
480 V 14.4 V 24.0 V

Those are the most volts you can lose before the circuit goes past the recommendation. The sections below show how to find the wire size that stays inside them.

What the NEC says

The NEC gives these figures in informational notes, not in the mandatory text. The note to 210.19(A) says branch-circuit conductors should be sized so that the voltage drop at the farthest outlet is no more than 3 %, and that the total drop on the feeder and the branch circuit together should not exceed 5 %. A matching note under 215.2(A) gives the same 3 % and 5 % for feeders. Informational notes explain and recommend, and the code does not enforce them. The numbers become enforceable when your project specification, a local amendment or the authority having jurisdiction adopts them, which many do. The note numbering changes between editions, so look up the current one in your copy.

The reason for the recommendation is performance, not safety. Motors lose torque and run hot at low voltage, lamps dim, and electronics can drop out. Voltage drop does not trip a breaker, and a circuit that carries current safely can still be a bad installation.

Formulas

Single-phase or DC: Vdrop = 2 × K × I × L / CM
Three-phase: Vdrop = √3 × K × I × L / CM
Percent drop = Vdrop / Vsource × 100

K is the resistivity of the conductor in ohm-circular mils per foot. A common working value is 12.9 for copper and 21.2 for aluminium at 75 °C, which covers the small extra resistance of stranded wire. I is the load current in amps, L the one-way length in feet, and CM the conductor’s circular mil area. Common values for copper wire are 4,110 CM for 14 AWG, 6,530 for 12 AWG, 10,380 for 10 AWG, 16,510 for 8 AWG, 26,240 for 6 AWG and 41,740 for 4 AWG. For larger conductors on AC, reactance adds to the drop, and the NEC conductor tables in Chapter 9 give resistance and reactance per 1,000 ft for a more exact figure.

Worked example 1: a 120 V branch circuit

A 20 A load sits 100 ft from the panel on a 120 V circuit, with copper wire.

The breaker and the ampacity table allow 12 AWG on a 20 A circuit, and many electricians would stop there. The voltage drop target is what pushes the wire up two sizes. The breaker size and wire ampacity still have to be checked separately.

Worked example 2: a three-phase feeder

A 50 A load at 208 V three-phase, 150 ft from the source.

This is a typical case where the answer sits on the edge of the limit, so round up to the next size.

How far can a circuit run?

The longest one-way run for a 3 % drop on a 120 V single-phase copper circuit at a given current:

Wire 15 A 20 A
14 AWG 38 ft not used on 20 A
12 AWG 61 ft 46 ft
10 AWG 97 ft 72 ft
8 AWG 154 ft 115 ft

On a 240 V circuit carrying the same current, the allowed drop in volts is twice as large, so the lengths double. These lengths assume the circuit carries its full rated current, which many circuits do not. A circuit that loads at half its rating can run about twice as far.

How to apply the 3 % and 5 %

The voltage drop calculator works with AWG or mm², includes temperature and reactance, and gives a slightly different answer from the rounded K values used here. The wire size calculator combines the drop check with the NEC ampacity.

Common mistakes

Questions

Is 5 % voltage drop acceptable?

It is the commonly used limit for the whole path from the service to the farthest outlet, with 3 % of it on any one feeder or branch circuit. Whether it is acceptable for your job depends on the load and the specification. A motor starting across a long feeder or sensitive electronics may need less.

Is voltage drop an NEC requirement?

Not as a general rule. The 3 % and 5 % figures are in informational notes. They become requirements when a specification or local rule adopts them. A few other sections, for specific equipment, have their own limits.

What is an acceptable voltage drop?

3 % on a feeder or branch circuit and 5 % overall is the commonly used target. Sensitive equipment, long motor starts and critical loads may call for less.

Is there a stricter limit for sensitive electronic equipment?

Yes. The NEC section on sensitive electronic equipment (647.4(D)) sets 1.5 % on a branch circuit and 2.5 % for feeder and branch together. Check the section number and values in your adopted edition before relying on them.

Does voltage drop affect breaker size?

No. The breaker is chosen from the load and the conductor’s ampacity. Voltage drop only changes how large the wire needs to be.

Do I use the load current or the breaker rating?

The load current, unless you are designing for the circuit to carry its full rating.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.