Voltage Drop Chart for Copper and Aluminum Wire

Volts dropped per amp per 100 ft for AWG 14 to 4/0 copper and aluminum, plus the longest run for a 3 % drop at 120 V and 240 V, with a worked example.

Updated 2026-11-23

ElectricalFree, no sign-upWorked examples

Voltage drop is the voltage lost along a wire because of its resistance. These charts give it for common AWG sizes in feet and amps, so you can check a run without a calculator. Values are for a two-wire circuit, with the length of the return conductor counted, and for conductors at 75 °C.

Volts dropped per ampere for each 100 ft of one-way run (out and back counted), conductors at 75 °C
AWGCopperAluminium
140.6141.012
120.3860.636
100.2430.400
80.1530.252
60.0960.158
40.0600.100
30.0480.079
20.0380.063
10.0300.050
1/00.0240.039
2/00.0190.031
3/00.0150.025
4/00.0120.020

Multiply the table value by the current in amps and by the one-way length in hundreds of feet.

Longest one-way run in feet for a 3 % drop, copper at 75 °C, 240 V single-phase
AWG15 A20 A30 A50 A
1478593923
12124936237
101981489959
831423615794
6500375250150
4794596397238
31,002751501300
21,263947631379
11,5931,194796478
1/02,0081,5061,004602
2/02,5321,8991,266760
3/03,1932,3951,597958
4/04,0263,0202,0131,208
Longest one-way run in feet for a 3 % drop, copper at 75 °C, 120 V single-phase
AWG15 A20 A
143929
126247
109974
8157118
6250187
4397298
3501376
2631474
1796597
1/01,004753
2/01,266950
3/01,5971,197
4/02,0131,510

How the numbers are calculated

Vdrop = 2 × I × L × ρ / A

I is the current, L the one-way length, A the conductor area and ρ the resistivity at the conductor temperature (0.017241 Ω·mm²/m for copper and 0.028264 for aluminum at 20 °C, raised for 75 °C). Reactance is ignored, which is accurate for short single-phase runs in small wire and understates the drop in large conductors. The maximum lengths are the length where the drop reaches 3 % of the supply voltage.

Worked example

A 20 A load sits 150 ft from the panel on a 240 V circuit in 10 AWG copper. The drop is 0.243 × 20 × 1.5 = 7.3 V, or 3.0 % of 240 V, so the run is at the limit. The chart agrees: the longest 10 AWG run at 20 A is 148 ft.

The same 20 A load, 150 ft away on a 120 V circuit, drops the same 7.3 V, but that is 6.1 % of 120 V. Moving to 6 AWG cuts it to 0.096 × 20 × 1.5 = 2.9 V, or 2.4 %. A higher supply voltage or a larger conductor both fix the problem.

What the NEC says

The NEC does not set a mandatory voltage drop limit for ordinary circuits. It recommends in informational notes a maximum of 3 % for a branch circuit and 5 % for feeder and branch together. The details are in the NEC voltage drop guide.

What the chart leaves out

Questions

What size wire for 100 ft at 20 amps?

At 240 V, 12 AWG gives 0.386 × 20 × 1 = 7.7 V which is 3.2 %, so 10 AWG is the next choice with 4.9 V (2.0 %). At 120 V the same run needs 8 AWG for under 3 %.

Is aluminum drop higher than copper?

About 65 % higher at the same size, because aluminum resistivity is higher. A larger aluminum size gives the same drop as copper.

Does the drop change with temperature?

Yes. A hot conductor has higher resistance. The chart uses 75 °C. At 20 °C the drop is about 18 % lower.

Voltage drop limits by application

Application Recommended limit Standard
NEC branch circuit 3 % NEC informational note to 210.19(A)
NEC feeder + branch combined 5 % NEC informational note to 215.2(A)
NEC sensitive electronic equipment 2.5 % NEC 647.4
IEC 60364 (residential, lighting) 3 % IEC 60364-5-52
IEC 60364 (industrial, motor) 5 % IEC 60364-5-52
Solar PV DC wiring 1–2 % NEC 690.8 guidance
Battery-to-inverter 0.5–1 % Manufacturer requirement

A motor that starts under voltage draw 50–60 % more starting current, so voltage drop matters more for motor circuits than for heaters. At 95 % of rated voltage a motor still starts; at 90 % it may not.

Worked example: subpanel feeder

A workshop subpanel sits 200 ft from the main panel and is fed at 240 V with a 60 A continuous load.

Allowed drop: 3 % of 240 V = 7.2 V. Combined feeder + branch limit is 5 %, so the feeder gets 2–3 %.

Formula: Area (kcmil) = 2 × L × I × K / (V × %drop / 100), where K = 12.9 for copper at 75 °C. Area = 2 × 200 × 60 × 12.9 / (240 × 3) = 86 kcmil.

Closest AWG: 2 AWG copper (66.4 kcmil) drops 4.0 %. 1 AWG (83.7 kcmil) drops 3.2 %. 1/0 AWG (105.6 kcmil) drops 2.5 %. For the 3 % limit, 1 AWG is the minimum.

Check against ampacity: 1 AWG THHN at 75 °C = 130 A, well above 60 A continuous × 1.25 = 75 A. The drop governs, not the ampacity.

Copper vs aluminum voltage drop

Aluminum has 61 % of copper’s conductivity, so the same wire size drops 1.64× more. To match copper’s drop, choose aluminum two AWG sizes larger:

Copper Aluminum equivalent Voltage drop match
12 AWG 10 AWG Al ±2 %
10 AWG 8 AWG Al ±2 %
8 AWG 6 AWG Al ±3 %
6 AWG 4 AWG Al ±2 %
4 AWG 2 AWG Al ±2 %
2 AWG 1/0 AWG Al ±2 %

Aluminum feeders of 100 A and above are common and cost-effective where the extra two AWG sizes fit the conduit. Aluminum is not permitted for 15 and 20 A branch circuits under NEC 310.106(B).

EV charger and motor circuit drop considerations

EV charger (Level 2, 7.6 kW, 240 V, 32 A): At 100 ft on 10 AWG copper, drop = 0.243 × 32 × 1 = 7.8 V = 3.2 % of 240 V. Use 8 AWG for 100 ft or longer runs (4.9 V = 2.0 %).

Heat pump motor (5 hp, 240 V, 28 A, NEC table current): At 150 ft on 10 AWG, drop = 0.243 × 28 × 1.5 = 10.2 V = 4.3 % — over the 3 % limit. Use 8 AWG: 0.096 × 28 × 1.5 = 4.0 V = 1.7 %.

More Q&As

Does the 3 % limit apply to 240 V and 120 V circuits the same way?

The percentage is the same, but the allowable volts differ: 3 % of 240 V = 7.2 V, while 3 % of 120 V = 3.6 V. A 120 V circuit has half the voltage to spend, so for the same current and wire size it reaches the limit at half the distance.

How do I apply the chart to a three-phase circuit?

Multiply the two-wire drop by 0.866 for a balanced three-phase circuit. 10 AWG at 20 A per phase over 100 ft drops 0.243 × 20 × 1 × 0.866 = 4.2 V on a 240 V three-phase system (1.75 %).

Does voltage drop affect energy bills?

Yes, but the effect is small on a typical branch circuit. A 3 % drop means 3 % of the circuit’s power is dissipated in the wire as heat rather than delivered to the load. On a 2,000 W circuit running 8 h/day, that is 60 W × 8 h = 480 Wh/day wasted. At $0.15/kWh that is $26/year — usually less than the cost of the larger wire.

Related calculators