Voltage drop is the voltage lost along a wire because of its resistance. These charts give it for common AWG sizes in feet and amps, so you can check a run without a calculator. Values are for a two-wire circuit, with the length of the return conductor counted, and for conductors at 75 °C.
| AWG | Copper | Aluminium |
|---|---|---|
| 14 | 0.614 | 1.012 |
| 12 | 0.386 | 0.636 |
| 10 | 0.243 | 0.400 |
| 8 | 0.153 | 0.252 |
| 6 | 0.096 | 0.158 |
| 4 | 0.060 | 0.100 |
| 3 | 0.048 | 0.079 |
| 2 | 0.038 | 0.063 |
| 1 | 0.030 | 0.050 |
| 1/0 | 0.024 | 0.039 |
| 2/0 | 0.019 | 0.031 |
| 3/0 | 0.015 | 0.025 |
| 4/0 | 0.012 | 0.020 |
Multiply the table value by the current in amps and by the one-way length in hundreds of feet.
| AWG | 15 A | 20 A | 30 A | 50 A |
|---|---|---|---|---|
| 14 | 78 | 59 | 39 | 23 |
| 12 | 124 | 93 | 62 | 37 |
| 10 | 198 | 148 | 99 | 59 |
| 8 | 314 | 236 | 157 | 94 |
| 6 | 500 | 375 | 250 | 150 |
| 4 | 794 | 596 | 397 | 238 |
| 3 | 1,002 | 751 | 501 | 300 |
| 2 | 1,263 | 947 | 631 | 379 |
| 1 | 1,593 | 1,194 | 796 | 478 |
| 1/0 | 2,008 | 1,506 | 1,004 | 602 |
| 2/0 | 2,532 | 1,899 | 1,266 | 760 |
| 3/0 | 3,193 | 2,395 | 1,597 | 958 |
| 4/0 | 4,026 | 3,020 | 2,013 | 1,208 |
| AWG | 15 A | 20 A |
|---|---|---|
| 14 | 39 | 29 |
| 12 | 62 | 47 |
| 10 | 99 | 74 |
| 8 | 157 | 118 |
| 6 | 250 | 187 |
| 4 | 397 | 298 |
| 3 | 501 | 376 |
| 2 | 631 | 474 |
| 1 | 796 | 597 |
| 1/0 | 1,004 | 753 |
| 2/0 | 1,266 | 950 |
| 3/0 | 1,597 | 1,197 |
| 4/0 | 2,013 | 1,510 |
How the numbers are calculated
I is the current, L the one-way length, A the conductor area and ρ the resistivity at the conductor temperature (0.017241 Ω·mm²/m for copper and 0.028264 for aluminum at 20 °C, raised for 75 °C). Reactance is ignored, which is accurate for short single-phase runs in small wire and understates the drop in large conductors. The maximum lengths are the length where the drop reaches 3 % of the supply voltage.
Worked example
A 20 A load sits 150 ft from the panel on a 240 V circuit in 10 AWG copper. The drop is 0.243 × 20 × 1.5 = 7.3 V, or 3.0 % of 240 V, so the run is at the limit. The chart agrees: the longest 10 AWG run at 20 A is 148 ft.
The same 20 A load, 150 ft away on a 120 V circuit, drops the same 7.3 V, but that is 6.1 % of 120 V. Moving to 6 AWG cuts it to 0.096 × 20 × 1.5 = 2.9 V, or 2.4 %. A higher supply voltage or a larger conductor both fix the problem.
What the NEC says
The NEC does not set a mandatory voltage drop limit for ordinary circuits. It recommends in informational notes a maximum of 3 % for a branch circuit and 5 % for feeder and branch together. The details are in the NEC voltage drop guide.
What the chart leaves out
- Ampacity. A wire that satisfies the voltage drop may still be too small for the breaker, and the reverse. Check the ampacity separately. The 14 AWG row is shown for length only; small conductors have their own overcurrent limits.
- Three-phase. Multiply the single-phase drop by 0.866 for a balanced three-phase circuit at the same current.
- Resistance method. The guide uses the circular-mil constant K = 12.9, which is about 2 % higher than these exact values. Both are good estimates.
Questions
What size wire for 100 ft at 20 amps?
At 240 V, 12 AWG gives 0.386 × 20 × 1 = 7.7 V which is 3.2 %, so 10 AWG is the next choice with 4.9 V (2.0 %). At 120 V the same run needs 8 AWG for under 3 %.
Is aluminum drop higher than copper?
About 65 % higher at the same size, because aluminum resistivity is higher. A larger aluminum size gives the same drop as copper.
Does the drop change with temperature?
Yes. A hot conductor has higher resistance. The chart uses 75 °C. At 20 °C the drop is about 18 % lower.
Voltage drop limits by application
| Application | Recommended limit | Standard |
|---|---|---|
| NEC branch circuit | 3 % | NEC informational note to 210.19(A) |
| NEC feeder + branch combined | 5 % | NEC informational note to 215.2(A) |
| NEC sensitive electronic equipment | 2.5 % | NEC 647.4 |
| IEC 60364 (residential, lighting) | 3 % | IEC 60364-5-52 |
| IEC 60364 (industrial, motor) | 5 % | IEC 60364-5-52 |
| Solar PV DC wiring | 1–2 % | NEC 690.8 guidance |
| Battery-to-inverter | 0.5–1 % | Manufacturer requirement |
A motor that starts under voltage draw 50–60 % more starting current, so voltage drop matters more for motor circuits than for heaters. At 95 % of rated voltage a motor still starts; at 90 % it may not.
Worked example: subpanel feeder
A workshop subpanel sits 200 ft from the main panel and is fed at 240 V with a 60 A continuous load.
Allowed drop: 3 % of 240 V = 7.2 V. Combined feeder + branch limit is 5 %, so the feeder gets 2–3 %.
Formula: Area (kcmil) = 2 × L × I × K / (V × %drop / 100), where K = 12.9 for copper at 75 °C. Area = 2 × 200 × 60 × 12.9 / (240 × 3) = 86 kcmil.
Closest AWG: 2 AWG copper (66.4 kcmil) drops 4.0 %. 1 AWG (83.7 kcmil) drops 3.2 %. 1/0 AWG (105.6 kcmil) drops 2.5 %. For the 3 % limit, 1 AWG is the minimum.
Check against ampacity: 1 AWG THHN at 75 °C = 130 A, well above 60 A continuous × 1.25 = 75 A. The drop governs, not the ampacity.
Copper vs aluminum voltage drop
Aluminum has 61 % of copper’s conductivity, so the same wire size drops 1.64× more. To match copper’s drop, choose aluminum two AWG sizes larger:
| Copper | Aluminum equivalent | Voltage drop match |
|---|---|---|
| 12 AWG | 10 AWG Al | ±2 % |
| 10 AWG | 8 AWG Al | ±2 % |
| 8 AWG | 6 AWG Al | ±3 % |
| 6 AWG | 4 AWG Al | ±2 % |
| 4 AWG | 2 AWG Al | ±2 % |
| 2 AWG | 1/0 AWG Al | ±2 % |
Aluminum feeders of 100 A and above are common and cost-effective where the extra two AWG sizes fit the conduit. Aluminum is not permitted for 15 and 20 A branch circuits under NEC 310.106(B).
EV charger and motor circuit drop considerations
EV charger (Level 2, 7.6 kW, 240 V, 32 A): At 100 ft on 10 AWG copper, drop = 0.243 × 32 × 1 = 7.8 V = 3.2 % of 240 V. Use 8 AWG for 100 ft or longer runs (4.9 V = 2.0 %).
Heat pump motor (5 hp, 240 V, 28 A, NEC table current): At 150 ft on 10 AWG, drop = 0.243 × 28 × 1.5 = 10.2 V = 4.3 % — over the 3 % limit. Use 8 AWG: 0.096 × 28 × 1.5 = 4.0 V = 1.7 %.
More Q&As
Does the 3 % limit apply to 240 V and 120 V circuits the same way?
The percentage is the same, but the allowable volts differ: 3 % of 240 V = 7.2 V, while 3 % of 120 V = 3.6 V. A 120 V circuit has half the voltage to spend, so for the same current and wire size it reaches the limit at half the distance.
How do I apply the chart to a three-phase circuit?
Multiply the two-wire drop by 0.866 for a balanced three-phase circuit. 10 AWG at 20 A per phase over 100 ft drops 0.243 × 20 × 1 × 0.866 = 4.2 V on a 240 V three-phase system (1.75 %).
Does voltage drop affect energy bills?
Yes, but the effect is small on a typical branch circuit. A 3 % drop means 3 % of the circuit’s power is dissipated in the wire as heat rather than delivered to the load. On a 2,000 W circuit running 8 h/day, that is 60 W × 8 h = 480 Wh/day wasted. At $0.15/kWh that is $26/year — usually less than the cost of the larger wire.