Working in mm² with IEC 60364? Use the cable size calculator.
Choosing a conductor under the NEC is a handful of separate checks, and the one that asks for the largest cable decides the size. This calculator runs the checks for you and shows which one governed, so you can see why a result came out larger than you expected.
The checks
(b) ampacity in the insulation column × kambient × kadjustment ≥ Icontinuous + Inoncontinuous
(c) optional: voltage drop ≤ the limit you set
Check (a) applies the 125 % rule to continuous loads and reads the ampacity from the temperature column that matches the equipment terminals, under 110.14(C) and 210.19(A)(1). Terminals on circuits up to 100 A are commonly treated as 60 °C unless the equipment is marked for 75 °C, and above 100 A as 75 °C. Check the markings on your equipment.
Check (b) lets a conductor with 90 °C insulation start from the 90 °C column, then reduces that value for ambient temperature (Table 310.15(B)(1)(1), which is Table 310.15(B)(2)(a) in the 2020 code) and for more than three current-carrying conductors in a raceway (310.15(C)(1)). The corrected ampacity must still carry the load itself. The 125 % factor is not applied here.
Check (c) uses the resistance of the conductor at 75 °C, the length you enter and the supply voltage.
Worked examples
A 40 A continuous load, copper, 75 °C terminals, 90 °C insulation, 30 °C ambient, three conductors. Check (a): 1.25 × 40 = 50 A. In the 75 °C column, 8 AWG carries 50 A. Check (b): 40 A at 90 °C is met by 10 AWG (40 A). The result is 8 AWG, set by the termination.
The same load on 60 °C terminals. The 60 °C column gives 55 A for 6 AWG, so the result is 6 AWG. This is why the equipment markings matter.
The same load, ambient 41 to 45 °C, four to six conductors in the raceway. The factors are 0.87 and 0.80, so k = 0.696. The 90 °C column must supply 40 / 0.696 = 57.5 A. 8 AWG (55 A × 0.696 = 38.3 A) is too small and 6 AWG (75 A × 0.696 = 52.2 A) works, so derating governs and the result is 6 AWG.
A long run. 40 A at 240 V single-phase over 200 ft with a 3 % drop limit needs about 14.2 mm² of copper. 6 AWG is 13.3 mm², which is too small, and 4 AWG at 21.2 mm² is the next size, so voltage drop governs.
What the result means
The result is the minimum conductor size under these checks. It is not a complete circuit design. The overcurrent device is chosen separately; the breaker size calculator applies the 125 % rule to it. Small conductors have extra limits on the device rating in 240.4(D): 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper. The calculator doesn’t apply these.
Not modelled
- Motor circuits, which follow Article 430.
- Parallel conductors. Sizes above 500 kcmil are outside the calculator.
- Conductor type details, such as special rules for cables, flexible cords and some tray wiring.
- Equipment grounding conductor sizing, which uses Table 250.122.
- Solid versus stranded resistance in the voltage-drop check. The calculation uses the nominal area, so a stranded conductor’s real drop is slightly higher.
Common mistakes
- Using the 90 °C column for the whole selection. The termination limit still applies.
- Applying derating to the 125 % value. Check (b) uses the plain load.
- Counting only the phase conductors. Neutrals that carry current count toward the adjustment factor, subject to the code’s rules.
- Ignoring length. A conductor that passes (a) and (b) can still lose too much voltage.
Questions
What wire size for a 50 A circuit?
For a noncontinuous 50 A load on 75 °C terminals, 8 AWG copper (50 A) works. For a 50 A continuous load, the 125 % rule needs 62.5 A and the result is 6 AWG on 75 °C terminals.
Can I use a smaller wire than the table size on a long run?
No. A longer run needs the same or a larger conductor, never a smaller one.
Does aluminum use the same table?
Yes, with lower ampacity values. Choose aluminum in the calculator. Check that the terminals are rated for it.
Which NEC edition do the section numbers follow?
The site follows the latest edition, the 2023 NEC. Where 2020 numbering differs, the page says so: the ambient correction table is 310.15(B)(2)(a) in 2020 and the adjustment table is 310.15(B)(3)(a). The table values were compared with the 2020 code. Check the section references against the edition your jurisdiction has adopted.
NEC Table 310.16 — copper conductor ampacity
The table below shows the base ampacity for copper conductors, taken from NEC Table 310.16, before any temperature or bundling corrections. Use the column that matches the lower of the conductor’s temperature rating and the equipment terminal’s rating.
| AWG / kcmil | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A |
| 12 AWG | 20 A | 25 A | 30 A |
| 10 AWG | 30 A | 35 A | 40 A |
| 8 AWG | 40 A | 50 A | 55 A |
| 6 AWG | 55 A | 65 A | 75 A |
| 4 AWG | 70 A | 85 A | 95 A |
| 3 AWG | 85 A | 100 A | 110 A |
| 2 AWG | 95 A | 115 A | 130 A |
| 1 AWG | 110 A | 130 A | 150 A |
| 1/0 AWG | 125 A | 150 A | 170 A |
| 2/0 AWG | 145 A | 175 A | 195 A |
| 3/0 AWG | 165 A | 200 A | 225 A |
| 4/0 AWG | 195 A | 230 A | 260 A |
Aluminum ampacity runs about 2–3 sizes lower for the same current: where 6 AWG copper carries 65 A at 75 °C, 4 AWG aluminum carries 65 A. The calculator handles aluminum separately.
The 60 °C column applies when the equipment is marked for 60 °C terminals, which is common on 15 A and 20 A residential devices. The 75 °C column applies on most modern circuit breakers above 100 A and on many terminals marked “AL/CU 75 °C”. Always check the terminal marking on the actual device — it overrides the table column you would otherwise use.
Sizing a wire for an EV charger circuit
EV charger circuits are a continuous load under NEC 625.42. The sequence:
- Find the charger’s rated output current from its nameplate. A 32 A charger is a continuous load.
- Apply the 125 % rule: 32 × 1.25 = 40 A minimum conductor rating. At 75 °C terminals, 8 AWG (50 A) is the minimum copper conductor — there is no 40 A entry in Table 310.16, so the next size up is 8 AWG.
- For a 50 ft run on a 240 V circuit, check voltage drop: round-trip = 100 ft. 8 AWG copper at 75 °C has 0.778 Ω/1,000 ft × 0.1 = 0.0778 Ω. Drop = 32 × 0.0778 = 2.49 V = 1.0 % — well within 3 %.
- For a 150 ft run: round-trip = 300 ft. Drop = 32 × 0.0778 × 3 = 7.47 V = 3.1 % — marginally over 3 %, so use 6 AWG.
| Charger output | Minimum conductor (75 °C) | Maximum run at 3 % (240 V) |
|---|---|---|
| 16 A | 12 AWG | ~135 ft |
| 24 A | 10 AWG | ~110 ft |
| 32 A | 8 AWG | ~140 ft |
| 40 A | 8 AWG | ~110 ft |
| 48 A | 6 AWG | ~120 ft |
Sizing a wire for an outbuilding feeder
A detached garage or outbuilding feeder is a common design problem. Suppose the outbuilding has a 60 A subpanel, continuous loads of 30 A and noncontinuous loads of 10 A, over 120 ft (one-way).
Check (a) — termination limit: 1.25 × 30 + 10 = 47.5 A. The next conductor at 75 °C is 8 AWG (50 A) — passes.
Check (b) — derating: single circuit in conduit, 30 °C ambient, no derating needed. 8 AWG at 90 °C = 55 A ≥ 40 A load — passes.
Check (c) — voltage drop: round-trip = 240 ft. At 40 A total load through 8 AWG (0.778 Ω/1,000 ft): drop = 40 × 0.778 × 0.24 = 7.47 V = 3.1 % on 240 V — just over 3 %. Upgrade to 6 AWG.
Result: 6 AWG copper — voltage drop governs, not ampacity. This is the most common outcome on longer rural runs. The calculator shows which check governed, which is what you need to explain the result to an inspector.
Temperature derating — common correction factors
When more than three current-carrying conductors share a raceway, or when the ambient temperature exceeds 30 °C (86 °F), the base ampacity must be derated. The two factors multiply together.
Ambient temperature correction (copper, 90 °C insulation), from NEC Table 310.15(B)(1)(1):
| Ambient (°C) | Ambient (°F) | Correction factor |
|---|---|---|
| 21–25 | 70–77 | 1.04 |
| 26–30 | 78–86 | 1.00 |
| 31–35 | 87–95 | 0.96 |
| 36–40 | 96–104 | 0.91 |
| 41–45 | 105–113 | 0.87 |
| 46–50 | 114–122 | 0.82 |
Bundling adjustment (NEC 310.15(C)(1)):
| Current-carrying conductors in raceway | Adjustment factor |
|---|---|
| 4–6 | 0.80 |
| 7–9 | 0.70 |
| 10–20 | 0.50 |
| 21–30 | 0.45 |
If the ambient is 40 °C and there are 5 conductors in the raceway, the combined factor is 0.91 × 0.80 = 0.73. The 90 °C ampacity must be divided by 0.73 to find the minimum column value: for a 40 A load, the 90 °C ampacity must be at least 40 / 0.73 = 54.8 A, which requires 6 AWG (75 A at 90 °C).
More Q&As
What wire size do I need for a 100 A service or subpanel?
For 100 A at 75 °C terminals (the standard for panels), 3 AWG copper (100 A at 75 °C) meets the ampacity requirement. For a long run with significant voltage drop, 2 AWG or 1 AWG may be needed. The calculator handles this directly.
Can I use 14 AWG for a 20 A circuit?
No. Under NEC 240.4(D), 14 AWG copper is limited to a 15 A overcurrent device regardless of the calculated ampacity. For a 20 A circuit, 12 AWG is the minimum.
What is the difference between wire size and cable size?
Wire size usually refers to individual conductors (AWG, kcmil). Cable size refers to the whole assembly — conductors plus insulation plus jacket — often specified in mm² under IEC standards. The cable size calculator works in mm² for IEC installations.
Does wire size change with AC frequency?
Not meaningfully at power frequencies (50 or 60 Hz). Skin effect is negligible in copper conductors at standard power frequencies. High-frequency applications are a different matter.
Related calculators
Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.