Calculator

Fault Current at the End of a Cable

Calculate the three-phase fault current at the end of a cable, including source, transformer and cable impedance, with peak and minimum values.

Updated 2026-10-08

Protection and MVFree, no sign-upFormula and worked example
Fault at the transformer terminals29.09 kA
Fault at the end of the cable9.83 kA
Peak current at the cable end14.20 kA
Minimum fault, hot cable7.52 kA
Peak factor (kappa)1.022

The fault level at a transformer is the highest the system can produce. Move down a cable and it drops, often by a large factor, because the cable adds resistance and reactance in series. That lower value matters twice: the devices at the cable end can be rated for less, and the protection must still see the smallest fault that can occur there. This calculator follows the simplified IEC 60909 method and gives the maximum, the peak and the minimum.

Method

Zsource = c × Un² / Sk″
Ztransformer = (z% / 100) × Un² / Str
Zcable = R + jX, R = ρ × L / (A × n)
Ik″ = c × Un / (√3 × |Z|)
ip = κ × √2 × Ik″, κ = 1.02 + 0.98 × e−3R/X

The source and transformer impedances are split into resistance and reactance using their X/R ratios. All resistances in the path are added, all reactances are added, and the magnitude of the total gives the fault current. Un is the line-to-line voltage, Sk″ the source fault level, Str the transformer rating, L the cable length, A its cross-section and n the number of cables in parallel. The voltage factor c is 1.05 for the maximum fault. For the minimum fault the calculator uses 0.95 and the cable resistance at the temperature you enter, because a hot cable has higher resistance.

Worked example

A 1,000 kVA, 5 % transformer on a 400 V system fed from a 500 MVA source, with 30 m of 25 mm² copper cable (0.08 Ω/km).

A short 25 mm² cable cuts the fault level by two thirds, because its resistance is more than twice the transformer’s impedance. Over a longer or thinner cable the effect is stronger still.

How to use the results

What this does not cover

For a final design, use a short-circuit study that follows the standard your project cites.

Common mistakes

Questions

Why does fault current fall along a cable?

The cable’s resistance and reactance add to the impedance in the fault path, so less current flows.

What source fault level should I use?

The value from the utility, in MVA or as a current in kA at the connection point. Leave it empty for an infinite bus, which gives the highest possible result.

What is the peak factor?

The ratio between the first-cycle peak and the steady RMS fault current. It depends on how resistive the path is, and it is smaller at the end of a cable than at the transformer.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.