The fault level at a transformer is the highest the system can produce. Move down a cable and it drops, often by a large factor, because the cable adds resistance and reactance in series. That lower value matters twice: the devices at the cable end can be rated for less, and the protection must still see the smallest fault that can occur there. This calculator follows the simplified IEC 60909 method and gives the maximum, the peak and the minimum.
Method
Ztransformer = (z% / 100) × Un² / Str
Zcable = R + jX, R = ρ × L / (A × n)
Ik″ = c × Un / (√3 × |Z|)
ip = κ × √2 × Ik″, κ = 1.02 + 0.98 × e−3R/X
The source and transformer impedances are split into resistance and reactance using their X/R ratios. All resistances in the path are added, all reactances are added, and the magnitude of the total gives the fault current. Un is the line-to-line voltage, Sk″ the source fault level, Str the transformer rating, L the cable length, A its cross-section and n the number of cables in parallel. The voltage factor c is 1.05 for the maximum fault. For the minimum fault the calculator uses 0.95 and the cable resistance at the temperature you enter, because a hot cable has higher resistance.
Worked example
A 1,000 kVA, 5 % transformer on a 400 V system fed from a 500 MVA source, with 30 m of 25 mm² copper cable (0.08 Ω/km).
- Source impedance: 1.05 × 400² / 500,000,000 = 0.000336 Ω.
- Transformer impedance: 0.05 × 400² / 1,000,000 = 0.008 Ω.
- Cable: R = 0.017241 / 25 × 30 = 0.0207 Ω and X = 0.0024 Ω.
- Fault at the transformer terminals: 29.1 kA.
- Fault at the cable end: 9.83 kA, about a third of the value at the transformer.
- Peak at the cable end: κ = 1.022, so ip = 14.2 kA.
- Minimum fault with the cable at 80 °C and c = 0.95: 7.52 kA.
A short 25 mm² cable cuts the fault level by two thirds, because its resistance is more than twice the transformer’s impedance. Over a longer or thinner cable the effect is stronger still.
How to use the results
- Breaking capacity at the cable end. The device there must be rated for at least the maximum fault at its own location, not the transformer value. The transformer value is the right figure for the device at the transformer.
- Making capacity. Breakers must also close onto the peak current, so compare their making rating with ip.
- Cable withstand. The cable itself must survive the fault for the clearing time, which depends on its short-time rating.
- Minimum fault and protection. An overcurrent device or relay must operate for the smallest fault it protects against. A long cable can bring the minimum fault so close to the setting that the protection is slow or does not operate.
What this does not cover
- Motor contribution. Running induction motors feed current into a fault for the first few cycles and can raise the maximum, mostly at motor control centres.
- The transformer correction factor. IEC 60909 applies a factor KT, slightly below 1 for a typical distribution transformer, to the transformer impedance. That lowers the impedance and raises the maximum fault by a few percent. It is left out here, so the maximum values can come out a few percent low. Allow for this when comparing against an equipment rating.
- Earth faults and unbalanced faults. Only the three-phase fault is calculated.
- Several sources or loops. The method assumes one radial path.
For a final design, use a short-circuit study that follows the standard your project cites.
Common mistakes
- Using the transformer value for devices downstream. Fault level falls along every cable.
- Ignoring parallel cables. Two cables in parallel halve the cable impedance, which raises the fault level at the end.
- Using cold resistance for the minimum fault. Use the cable temperature during the fault or just before it.
- Leaving out reactance. Reactance is small for a thin cable but matters for large conductors, where it can dominate.
Questions
Why does fault current fall along a cable?
The cable’s resistance and reactance add to the impedance in the fault path, so less current flows.
What source fault level should I use?
The value from the utility, in MVA or as a current in kA at the connection point. Leave it empty for an infinite bus, which gives the highest possible result.
What is the peak factor?
The ratio between the first-cycle peak and the steady RMS fault current. It depends on how resistive the path is, and it is smaller at the end of a cable than at the transformer.
Fault current reduction table — cable length vs. fault level
Remaining fault current at the cable end for a 1,000 kVA, 11 kV/400 V transformer (Zcc 6%, source fault level 500 MVA at 11 kV):
| Cable cross-section | Cable length | Fault current at end | Reduction from source |
|---|---|---|---|
| 25 mm² XLPE copper | 10 m | 20.3 kA | 10 % |
| 25 mm² XLPE copper | 30 m | 14.1 kA | 37 % |
| 25 mm² XLPE copper | 50 m | 10.8 kA | 52 % |
| 50 mm² XLPE copper | 50 m | 15.9 kA | 29 % |
| 95 mm² XLPE copper | 100 m | 17.4 kA | 22 % |
| 185 mm² XLPE copper | 100 m | 19.5 kA | 13 % |
Source fault level at 400 V bus ≈ 22.6 kA (1,000 kVA at 6% Zcc). Values indicative only; exact results depend on actual cable impedance data.
Worked example: board fault current 100 m from a 2,500 kVA transformer
A main LV switchboard is fed from a 2,500 kVA 11 kV/400 V transformer (Zcc = 6%), via 100 m of 240 mm² XLPE copper cable (R = 0.0754 Ω/km, X = 0.082 Ω/km per IEC 60228).
Step 1 — transformer impedance: Scc at transformer LV terminals = Sn / Zcc = 2,500 / 0.06 = 41,667 kVA. Transformer fault current = 41,667 × 1,000 / (√3 × 400) = 60.1 kA. Transformer impedance Ztr = 400² / (41,667 × 1,000) = 0.00384 Ω.
Step 2 — cable impedance: R = 0.0754 × 0.1 = 0.00754 Ω. X = 0.082 × 0.1 = 0.0082 Ω. Z_cable = √(0.00754² + 0.0082²) = 0.01115 Ω.
Step 3 — total impedance and fault current: Z_total = Ztr + Z_cable = 0.00384 + 0.01115 = 0.01499 Ω (approximate scalar addition). I_fault = 400 / (√3 × 0.01499) = 15.4 kA symmetrical RMS.
Step 4 — peak factor (κ, IEC 60909): R/X = (0.00384 + 0.00754) / (0.00384 + 0.0082) ≈ 0.94. κ ≈ 1.5 from IEC 60909 figure. Peak current = √2 × 1.5 × 15.4 = 32.7 kA.
The switchboard bus bars and circuit breakers must be rated for ≥ 15.4 kA RMS and ≥ 32.7 kA peak making capacity.
Cable thermal withstand check
After calculating the fault current, check that the cable can carry it for the protection operating time without overheating. The IEC adiabatic equation:
S ≥ I × √t / k
Where S is the cable cross-section in mm², I is the fault current in A, t is the clearing time in seconds, and k is a material constant (k = 143 for copper XLPE, 115 for copper PVC, 94 for aluminium XLPE).
Example: 25 mm² copper XLPE, 10 kA fault, 0.2 s clearing time. Required S = 10,000 × √0.2 / 143 = 10,000 × 0.447 / 143 = 31.3 mm². The 25 mm² cable fails the adiabatic check. Use 35 mm² (minimum 31.3 mm²).
Cable impedance data for common sizes (copper XLPE, 400 V)
| Cross-section | R at 90°C (Ω/km) | X (Ω/km) | Z (Ω/km) |
|---|---|---|---|
| 16 mm² | 1.380 | 0.097 | 1.383 |
| 25 mm² | 0.868 | 0.090 | 0.873 |
| 35 mm² | 0.627 | 0.085 | 0.633 |
| 50 mm² | 0.443 | 0.082 | 0.451 |
| 70 mm² | 0.313 | 0.080 | 0.323 |
| 95 mm² | 0.233 | 0.077 | 0.245 |
| 150 mm² | 0.149 | 0.075 | 0.168 |
| 240 mm² | 0.0754 | 0.082 | 0.112 |
Values at maximum operating temperature (90°C). R increases with temperature; use 20°C values × 1.28 to convert. Source: typical IEC 60228 Class 2 copper conductors.
More Q&As
Does the fault current at the end of a cable affect what breaker I need at the start?
No — the breaker at the start of the cable must interrupt the fault current at the source end (before the cable), which is the higher figure. The fault level at the cable end is what governs the ratings of the equipment connected there (switchgear, busbars, isolators).
My cable is 150 m — can I simply double the 75 m result?
Not exactly. Fault current is inversely proportional to total impedance, and the transformer impedance is a fixed offset. Doubling the cable doubles the cable’s contribution to total impedance, but the transformer’s contribution stays the same. The result is not half: it is Ztr / (Ztr + 2×Zcable) × original current.
What is “minimum fault current” and why does it matter?
Maximum fault current (three-phase symmetrical) governs equipment rupturing and making ratings. Minimum fault current (single-phase line-to-earth, or end-of-line two-phase) governs whether the protection actually operates within its clearing time for a bolted fault. If minimum fault current is too low, the IDMT relay or fuse may not clear the fault before the cable overheats.
Related calculators
Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.