Calculator

Fault Current at the End of a Cable

Calculate the three-phase fault current at the end of a cable, including source, transformer and cable impedance, with peak and minimum values.

Updated 2026-11-23

Protection and MVFree, no sign-upFormula and worked example
Fault at the transformer terminals29.09 kA
Fault at the end of the cable9.83 kA
Peak current at the cable end14.20 kA
Minimum fault, hot cable7.52 kA
Peak factor (kappa)1.022

The fault level at a transformer is the highest the system can produce. Move down a cable and it drops, often by a large factor, because the cable adds resistance and reactance in series. That lower value matters twice: the devices at the cable end can be rated for less, and the protection must still see the smallest fault that can occur there. This calculator follows the simplified IEC 60909 method and gives the maximum, the peak and the minimum.

Method

Zsource = c × Un² / Sk″
Ztransformer = (z% / 100) × Un² / Str
Zcable = R + jX, R = ρ × L / (A × n)
Ik″ = c × Un / (√3 × |Z|)
ip = κ × √2 × Ik″, κ = 1.02 + 0.98 × e−3R/X

The source and transformer impedances are split into resistance and reactance using their X/R ratios. All resistances in the path are added, all reactances are added, and the magnitude of the total gives the fault current. Un is the line-to-line voltage, Sk″ the source fault level, Str the transformer rating, L the cable length, A its cross-section and n the number of cables in parallel. The voltage factor c is 1.05 for the maximum fault. For the minimum fault the calculator uses 0.95 and the cable resistance at the temperature you enter, because a hot cable has higher resistance.

Worked example

A 1,000 kVA, 5 % transformer on a 400 V system fed from a 500 MVA source, with 30 m of 25 mm² copper cable (0.08 Ω/km).

A short 25 mm² cable cuts the fault level by two thirds, because its resistance is more than twice the transformer’s impedance. Over a longer or thinner cable the effect is stronger still.

How to use the results

What this does not cover

For a final design, use a short-circuit study that follows the standard your project cites.

Common mistakes

Questions

Why does fault current fall along a cable?

The cable’s resistance and reactance add to the impedance in the fault path, so less current flows.

What source fault level should I use?

The value from the utility, in MVA or as a current in kA at the connection point. Leave it empty for an infinite bus, which gives the highest possible result.

What is the peak factor?

The ratio between the first-cycle peak and the steady RMS fault current. It depends on how resistive the path is, and it is smaller at the end of a cable than at the transformer.

Fault current reduction table — cable length vs. fault level

Remaining fault current at the cable end for a 1,000 kVA, 11 kV/400 V transformer (Zcc 6%, source fault level 500 MVA at 11 kV):

Cable cross-section Cable length Fault current at end Reduction from source
25 mm² XLPE copper 10 m 20.3 kA 10 %
25 mm² XLPE copper 30 m 14.1 kA 37 %
25 mm² XLPE copper 50 m 10.8 kA 52 %
50 mm² XLPE copper 50 m 15.9 kA 29 %
95 mm² XLPE copper 100 m 17.4 kA 22 %
185 mm² XLPE copper 100 m 19.5 kA 13 %

Source fault level at 400 V bus ≈ 22.6 kA (1,000 kVA at 6% Zcc). Values indicative only; exact results depend on actual cable impedance data.

Worked example: board fault current 100 m from a 2,500 kVA transformer

A main LV switchboard is fed from a 2,500 kVA 11 kV/400 V transformer (Zcc = 6%), via 100 m of 240 mm² XLPE copper cable (R = 0.0754 Ω/km, X = 0.082 Ω/km per IEC 60228).

Step 1 — transformer impedance: Scc at transformer LV terminals = Sn / Zcc = 2,500 / 0.06 = 41,667 kVA. Transformer fault current = 41,667 × 1,000 / (√3 × 400) = 60.1 kA. Transformer impedance Ztr = 400² / (41,667 × 1,000) = 0.00384 Ω.

Step 2 — cable impedance: R = 0.0754 × 0.1 = 0.00754 Ω. X = 0.082 × 0.1 = 0.0082 Ω. Z_cable = √(0.00754² + 0.0082²) = 0.01115 Ω.

Step 3 — total impedance and fault current: Z_total = Ztr + Z_cable = 0.00384 + 0.01115 = 0.01499 Ω (approximate scalar addition). I_fault = 400 / (√3 × 0.01499) = 15.4 kA symmetrical RMS.

Step 4 — peak factor (κ, IEC 60909): R/X = (0.00384 + 0.00754) / (0.00384 + 0.0082) ≈ 0.94. κ ≈ 1.5 from IEC 60909 figure. Peak current = √2 × 1.5 × 15.4 = 32.7 kA.

The switchboard bus bars and circuit breakers must be rated for ≥ 15.4 kA RMS and ≥ 32.7 kA peak making capacity.

Cable thermal withstand check

After calculating the fault current, check that the cable can carry it for the protection operating time without overheating. The IEC adiabatic equation:

S ≥ I × √t / k

Where S is the cable cross-section in mm², I is the fault current in A, t is the clearing time in seconds, and k is a material constant (k = 143 for copper XLPE, 115 for copper PVC, 94 for aluminium XLPE).

Example: 25 mm² copper XLPE, 10 kA fault, 0.2 s clearing time. Required S = 10,000 × √0.2 / 143 = 10,000 × 0.447 / 143 = 31.3 mm². The 25 mm² cable fails the adiabatic check. Use 35 mm² (minimum 31.3 mm²).

Cable impedance data for common sizes (copper XLPE, 400 V)

Cross-section R at 90°C (Ω/km) X (Ω/km) Z (Ω/km)
16 mm² 1.380 0.097 1.383
25 mm² 0.868 0.090 0.873
35 mm² 0.627 0.085 0.633
50 mm² 0.443 0.082 0.451
70 mm² 0.313 0.080 0.323
95 mm² 0.233 0.077 0.245
150 mm² 0.149 0.075 0.168
240 mm² 0.0754 0.082 0.112

Values at maximum operating temperature (90°C). R increases with temperature; use 20°C values × 1.28 to convert. Source: typical IEC 60228 Class 2 copper conductors.

More Q&As

Does the fault current at the end of a cable affect what breaker I need at the start?

No — the breaker at the start of the cable must interrupt the fault current at the source end (before the cable), which is the higher figure. The fault level at the cable end is what governs the ratings of the equipment connected there (switchgear, busbars, isolators).

My cable is 150 m — can I simply double the 75 m result?

Not exactly. Fault current is inversely proportional to total impedance, and the transformer impedance is a fixed offset. Doubling the cable doubles the cable’s contribution to total impedance, but the transformer’s contribution stays the same. The result is not half: it is Ztr / (Ztr + 2×Zcable) × original current.

What is “minimum fault current” and why does it matter?

Maximum fault current (three-phase symmetrical) governs equipment rupturing and making ratings. Minimum fault current (single-phase line-to-earth, or end-of-line two-phase) governs whether the protection actually operates within its clearing time for a bolted fault. If minimum fault current is too low, the IDMT relay or fuse may not clear the fault before the cable overheats.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.