Calculator

AWG to mm² Converter

Convert any AWG gauge to mm² cross-section and diameter, or mm² back to AWG. Complete chart from 4/0 to 30 AWG with nearest metric size and the conversion formula.

Updated 2026-11-15

ElectricalFree, no sign-upFormula and worked example
AWG10
Area5.26 mm²
Diameter2.588 mm

American Wire Gauge is a logarithmic scale: each step down in gauge number increases the cross-section by about 26%, and every three steps roughly doubles it. Metric cables are specified by cross-sectional area in mm², in a different set of preferred sizes, so a conversion is always approximate in one direction.

Formula

d = 0.127 mm × 92(36 − n) / 39
A = π / 4 × d²

n is the gauge number. For 1/0, 2/0, 3/0 and 4/0, use n = 0, −1, −2 and −3. The diameter is that of a solid round conductor. The definition comes from the standard that fixes 4/0 at 0.46 inch and 36 at 0.005 inch.

Worked example

AWG 10: d = 0.127 × 92(26/39) = 0.127 × 20.38 = 2.588 mm.

A = π / 4 × 2.588² = 5.26 mm².

AWG 4/0: d = 11.684 mm, A = 107.2 mm². Both agree with the widely published gauge tables.

Reading the result

The calculator returns the nearest AWG to a given mm² size. That is a match by area, not a statement that the cables are interchangeable. If your design requires at least 6 mm², AWG 9 (6.63 mm²) is the nearest, but AWG 10 (5.26 mm²) is smaller than the requirement. Round to the larger conductor when the area is a minimum.

Two further points matter when you compare cables:

AWG to mm² chart

Every standard size, solid round conductor, from the formula above. The last column is the smallest IEC 60228 preferred metric size that is at least as large, which is the safe choice when an area is a minimum.

AWG Diameter (mm) Diameter (in) Area (mm²) Smallest standard metric size at or above
4/0 11.684 0.4600 107.22 120 mm²
3/0 10.405 0.4096 85.03 95 mm²
2/0 9.266 0.3648 67.43 70 mm²
1/0 8.251 0.3249 53.48 70 mm²
1 7.348 0.2893 42.41 50 mm²
2 6.544 0.2576 33.63 35 mm²
3 5.827 0.2294 26.67 35 mm²
4 5.189 0.2043 21.15 25 mm²
5 4.621 0.1819 16.77 25 mm²
6 4.115 0.1620 13.30 16 mm²
7 3.665 0.1443 10.55 16 mm²
8 3.264 0.1285 8.37 10 mm²
9 2.906 0.1144 6.63 10 mm²
10 2.588 0.1019 5.26 6 mm²
11 2.305 0.0907 4.17 6 mm²
12 2.053 0.0808 3.31 4 mm²
13 1.828 0.0720 2.62 4 mm²
14 1.628 0.0641 2.08 2.5 mm²
15 1.450 0.0571 1.65 2.5 mm²
16 1.291 0.0508 1.31 1.5 mm²
17 1.150 0.0453 1.04 1.5 mm²
18 1.024 0.0403 0.823 1 mm²
19 0.912 0.0359 0.653 0.75 mm²
20 0.812 0.0320 0.518 0.75 mm²
21 0.723 0.0285 0.410 0.5 mm²
22 0.644 0.0253 0.326 0.5 mm²
23 0.573 0.0226 0.258 0.5 mm²
24 0.511 0.0201 0.205 0.5 mm²
26 0.405 0.0159 0.129 0.5 mm²
28 0.321 0.0126 0.081 0.5 mm²
30 0.255 0.0100 0.051 0.5 mm²

Sizes 25, 27 and 29 are rarely used and left out. The page is a size conversion only: it says nothing about how much current a conductor can carry.

mm² to AWG chart

For a metric size, the nearest AWG matches by area, and it can be slightly smaller. The next column gives the smallest AWG that is at least as large, which is the one to use when the metric size is a minimum.

Metric size Nearest AWG Area of nearest AWG (mm²) Smallest AWG with at least this area Its area (mm²)
0.5 mm² 20 0.52 20 0.52
0.75 mm² 18 0.82 18 0.82
1 mm² 17 1.04 17 1.04
1.5 mm² 15 1.65 15 1.65
2.5 mm² 13 2.62 13 2.62
4 mm² 11 4.17 11 4.17
6 mm² 9 6.63 9 6.63
10 mm² 7 10.55 7 10.55
16 mm² 5 16.77 5 16.77
25 mm² 3 26.67 3 26.67
35 mm² 2 33.63 1 42.41
50 mm² 1/0 53.48 1/0 53.48
70 mm² 2/0 67.43 3/0 85.03
95 mm² 3/0 85.03 4/0 107.22

Above 95 mm², 120 mm² needs 250 kcmil (126.7 mm²), because 4/0 is only 107.2 mm². American practice quotes large conductors in kcmil.

Metric preferred sizes

IEC 60228 preferred conductor sizes include 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185 and 240 mm². AWG sizes rarely land on one of these, which is why a design moved from one system to the other usually needs a fresh calculation and not just a conversion.

Large conductors in kcmil

Above 4/0, American practice quotes size in kcmil, thousands of circular mils. One kcmil is 0.5067 mm², so a 250 kcmil conductor has a nominal area of about 126.7 mm². This calculator covers AWG sizes from 4/0 up to 30 AWG.

Substituting one size for another

When a spec calls for a metric cable and only AWG is on hand, or the other way round, choose the size with the same or larger area. A smaller conductor has more resistance per metre, so for the same current it loses more voltage and runs hotter. The length also matters: a short run of a slightly undersized cable may be acceptable on paper, but the voltage drop and the code limits have to be checked in each case.

Questions

What is the metric equivalent of 12 AWG?

About 3.31 mm². The nearest common metric size is 4 mm², which is larger, while 2.5 mm² is smaller.

Is AWG 14 the same as 2.5 mm²?

No. AWG 14 is 2.08 mm² and 2.5 mm² is between AWG 13 and 14. In practice they are treated as roughly comparable for light circuits, but the allowable current differs by code.

Why do larger AWG numbers mean thinner wire?

The number counts the drawing steps through dies used in manufacture. More steps give thinner wire.

How do I read 4/0?

It is spoken “four-aught” and is the largest standard AWG size before sizes are quoted in kcmil. It is 107.2 mm².