Watts tell you how much power a load uses. Amps tell you how much current it draws, and that is the figure that sizes a breaker and a cable. The conversion depends on the voltage, and on AC it also depends on the power factor, so the same wattage draws very different currents on different supplies.
Formulas
AC single-phase: I = P / (V × PF)
AC three-phase: I = P / (√3 × VLL × PF)
I is current in amps, P is real power in watts, V is voltage and PF is the power factor from 0 to 1. For three-phase, VLL is the line-to-line voltage and I is the current in each line, assuming a balanced load. If your power is in kilowatts, use the kW to amps calculator, which is the same formula with the power entered in kW.
Worked examples
A 1,500 W heater on a 120 V single-phase supply, power factor 1:
I = 1,500 / 120 = 12.5 A. On 240 V the same heater draws 6.25 A.
A 3,000 W single-phase motor load on 240 V at a power factor of 0.9:
I = 3,000 / (240 × 0.9) = 13.89 A.
A 10,000 W three-phase load on 400 V at 0.8 power factor:
I = 10,000 / (1.732 × 400 × 0.8) = 18.04 A.
Current for common loads
At a power factor of 1, in amps:
| Power | 120 V | 208 V | 230 V | 240 V | 277 V |
|---|---|---|---|---|---|
| 1,000 W | 8.33 | 4.81 | 4.35 | 4.17 | 3.61 |
| 1,500 W | 12.50 | 7.21 | 6.52 | 6.25 | 5.42 |
| 2,000 W | 16.67 | 9.62 | 8.70 | 8.33 | 7.22 |
On a 12 V DC system, 100 W draws 8.33 A. At 24 V it draws 4.17 A and at 48 V 2.08 A, which is why higher-voltage DC systems need thinner cable for the same power.
From amps to a breaker
Once you have the current, the breaker and the cable follow. Under the NEC, a load that runs for three hours or more is a continuous load and the circuit must be rated for 125 % of it. The 1,500 W heater above draws 12.5 A, and 12.5 × 1.25 = 15.6 A, so a 15 A breaker is too small and the next standard size is 20 A. The breaker size calculator does this step for you.
Common mistakes
- Using the line-to-neutral voltage on three-phase. With the √3 formula, use the line-to-line voltage, such as 400 V or 208 V. Using 230 V understates the power, or overstates the current, by a factor of 1.732.
- Ignoring power factor. A motor load at 0.8 draws 25 % more current than the same watts at unity. Take the power factor from the nameplate or from a measurement.
- Confusing watts and volt-amps. A label that gives VA, as on many UPS units, is apparent power. The real power in watts is lower by the power factor.
- Sizing from the running current alone. Motors and compressors draw several times their running current for a moment at start, so a breaker or a generator sized to the running figure may trip.
Questions
How many amps is 1,000 watts?
At 120 V it is 8.33 A. At 230 V it is 4.35 A, and on a 12 V DC supply it is 83.3 A. The answer always depends on the voltage.
How many watts can a 15 A, 120 V circuit carry?
15 × 120 = 1,800 W at most. For a continuous load the practical limit is 80 % of that, 1,440 W, because the breaker must be 125 % of a continuous load.
Do watts to amps and kW to amps give the same answer?
Yes, if you enter the same power. 1,000 W is 1 kW, so both calculators agree.
Why does the power factor not appear for DC?
DC has no phase shift between voltage and current, so the power is simply volts times amps.
How many amps is a 1,500 W space heater?
On a 120 V circuit: 1,500 / 120 = 12.5 A. On 240 V: 6.25 A. Heaters are resistive (power factor 1), so voltage is the only variable.
How many amps does a 100 W light bulb use?
A 100 W incandescent on 120 V draws 0.83 A. An LED delivering the same light uses roughly 10–15 W, drawing 0.08–0.13 A.
How many amps is 2,000 watts on 240 V?
2,000 / 240 = 8.33 A for a resistive load. For an inductive load at 0.85 power factor: 2,000 / (240 × 0.85) = 9.80 A.
How do I size a circuit for a 2,000 W load?
If the load runs continuously: 2,000 W / 120 V = 16.67 A. Apply the 125 % rule: 16.67 × 1.25 = 20.8 A. Use a 25 A breaker (next standard size above 20.8 A) and a conductor rated for at least 25 A — 10 AWG at 75 °C covers 35 A and passes comfortably.
What is the current draw of a 5,000 W generator output?
At 240 V single-phase: 5,000 / 240 = 20.8 A. That is the output current. The generator’s input from the engine is higher by the alternator efficiency (typically 85–95 %).
Power factor — what it means in practice
Power factor is the ratio of real power (watts) to apparent power (volt-amps). A load with a power factor of 0.8 draws 25 % more current than the same wattage at unity power factor, because part of the current flows back and forth without doing work.
Typical power factors by load type:
| Load | Typical power factor |
|---|---|
| Resistive heaters, incandescent lighting | 1.00 |
| LED luminaires | 0.90–0.95 |
| Fluorescent lighting with electronic ballast | 0.90–0.95 |
| Induction motors at full load | 0.85–0.92 |
| Induction motors at 50 % load | 0.70–0.80 |
| Variable-speed drives | 0.95–0.98 |
| UPS systems at load | 0.90–0.99 |
| Welding equipment | 0.50–0.70 |
For lighting and heating circuits, power factor is effectively 1.0 and the simple P / V formula is accurate. For motor loads, nameplate power factor must be used or the current will be understated. Many industrial meters show power factor directly; for a home circuit a clamp meter measuring both watts and volt-amps will give it.
Sizing a circuit from watts — the full NEC sequence
Converting watts to amps is step one of sizing a circuit. The full sequence under NEC Article 210:
- Calculate the running current: I = P / (V × PF) for single-phase AC.
- Apply the continuous-load multiplier: if the load runs for three hours or more, multiply by 1.25 per NEC 210.20(A).
- Select the breaker: next standard size at or above the multiplied current (NEC 240.6(A)). Standard sizes: 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 A.
- Select the conductor: ampacity from NEC Table 310.12 must equal or exceed the breaker size for most circuits. 12 AWG copper covers 20 A at 75 °C, 10 AWG covers 35 A, 8 AWG covers 50 A.
- Check voltage drop: for runs over 50 ft, check that the drop stays under 3 % at the breaker rating. Use the voltage drop calculator.
Example — 2,400 W continuous resistive load on 240 V:
Running current: 2,400 / 240 = 10 A. Continuous multiplier: 10 × 1.25 = 12.5 A. Breaker: 15 A (next standard above 12.5). Conductor: 14 AWG at 75 °C covers 15 A — acceptable. For a 100 ft run: loop = 200 ft, 14 AWG resistance at 75 °C = 3.071 Ω/1,000 ft × 0.2 = 0.614 Ω, voltage drop = 10 × 0.614 = 6.14 V or 2.6 % — passes 3 % target.
Real power, apparent power and VA ratings
Many devices — UPS units, generators, transformers — are rated in volt-amps (VA) rather than watts. VA is the apparent power, which includes both the real power doing work and the reactive power circulating in the system.
W = VA × PF
kVAR = √(kVA² − kW²)
A 1,000 VA UPS at a power factor of 0.9 delivers 900 W of real power. The current it draws from the wall is 1,000 / 120 = 8.33 A, not 900 / 120 = 7.5 A. Sizing a UPS circuit from the watt rating understates the current. Always use the VA figure for circuit sizing.
Generators are rated in kVA at a stated power factor (typically 0.8 lagging). A 10 kVA generator at 0.8 PF delivers 8 kW. If the connected load totals 8 kW at 0.95 PF, the apparent power is 8 / 0.95 = 8.42 kVA — the generator has headroom. If the same 8 kW load is at 0.7 PF, the apparent power is 11.4 kVA, which overloads a 10 kVA generator even though the watts are within rating.
Low-voltage DC systems
On DC systems at 12 V, 24 V or 48 V, the same wattage produces much larger currents than on mains AC. This is why cable sizing on solar, RV, marine and telecom systems is critical.
| Power | 12 V | 24 V | 48 V | 120 V | 240 V |
|---|---|---|---|---|---|
| 100 W | 8.33 A | 4.17 A | 2.08 A | 0.83 A | 0.42 A |
| 500 W | 41.7 A | 20.8 A | 10.4 A | 4.17 A | 2.08 A |
| 1,000 W | 83.3 A | 41.7 A | 20.8 A | 8.33 A | 4.17 A |
| 3,000 W | 250 A | 125 A | 62.5 A | 25 A | 12.5 A |
A 3,000 W inverter running from a 12 V battery bank draws 250 A — a cable and connection size that surprises many first-time installers. At 48 V the same inverter draws 62.5 A, which is why 48 V is the standard bus voltage for larger off-grid and backup systems. The solar DC cable size calculator handles these low-voltage sizing problems with voltage drop included.