Calculator

Solar DC Cable Size Calculator

Find the minimum cable size for any solar or battery DC run. Enter amps, length and max voltage drop — get mm² or AWG with the formula shown.

Updated 2026-11-23

Solar and EVFree, no sign-upFormula and worked example
Minimum area3.73 mm²
Next IEC size4 mm² (drop 1.87 %)
Next AWG size10 AWG (drop 1.42 %)

Voltage drop only. Check the current rating of the chosen cable against the code tables before using it.

This calculator sizes a cable so the voltage lost along its length stays within a limit you choose. It is half of cable selection. The other half is current-carrying capacity, which depends on the insulation, how the cable is installed and the code in force, and it is not calculated here.

Formula

Area (mm²) = 2 × L × I × ρ / (V × allowed drop)
ρ = ρ20 × (1 + α × (T − 20))

L is the one-way length in metres, doubled because current flows out and back. I is the current, V the system voltage, and the allowed drop is a fraction (2 % is 0.02). ρ is the resistivity: 0.017241 Ω·mm²/m for copper at 20 °C and 0.028264 for aluminium, rising about 0.39 % per °C for copper and 0.40 % for aluminium. The calculator corrects for the conductor temperature you enter.

Worked example

A battery feed carries 10 A over 10 m at 48 V, with a 2 % allowed drop, copper conductors at 20 °C:

Area = 2 × 10 × 10 × 0.017241 / (48 × 0.02) = 3.59 mm².

At 30 °C the same calculation gives 3.73 mm². Either way the next IEC size is 4 mm² and the nearest AWG is 10. With 4 mm² at 20 °C the drop is 0.86 V, which is 1.8 % of 48 V (1.87 % at 30 °C).

Why voltage changes everything

The allowed drop is a percentage of the system voltage, so a low-voltage system has a small number of volts to spend. The same 10 A over 10 m at 12 V needs 14.4 mm², nearly four times the area. This is why solar strings run at hundreds of volts and why 48 V batteries are favoured over 12 V ones for larger systems.

What to choose as the allowed drop

There isn’t one legal figure for solar DC circuits. Designers commonly aim for 1 to 3 % on array wiring and a lower value on battery cables, where the current is high and the loss is a straight waste of stored energy. The NEC’s informational notes suggest a total of 5 % for feeders plus branch circuits, which is guidance, not a rule for PV. Check the standard or the equipment manufacturer’s requirement for your project.

The ampacity check

After the drop calculation, check the cable’s current rating. For PV circuits, the code applies multipliers to the array’s short-circuit current when sizing conductors and protective devices (see NEC 690.8), and the result is larger than the running current. The cable must also be rated for the temperature, the sunlight and the installation method. Use PV-rated cable, for example EN 50618 H1Z2Z2-K in Europe or USE-2/PV wire in the US, for exposed array wiring. Take the final size as the larger of the two results.

Common mistakes

Questions

What size wire for a 100 W panel at 12 V over 5 m?

A 12 V nominal 100 W panel is typically rated around 6 A. At a 3 % allowed drop, copper at 30 °C needs about 3.0 mm², so 4 mm² is the nearest size up, subject to the ampacity check.

Is aluminium acceptable?

It is used for large feeders. It needs about 1.64 times the area of copper for the same drop, and its terminations need parts rated for aluminium.

Does the temperature setting matter?

Modestly. A hot conductor has higher resistance, so use a realistic operating temperature, not 20 °C.

Solar DC cable sizing reference table

Minimum copper cable area (mm²) for a 2% voltage drop at 25°C, for common PV system voltages:

Current 5 m one-way 10 m 15 m 20 m 30 m
12 V system
5 A 1.0 mm² 2.5 mm² 4.0 mm² 6.0 mm² 10 mm²
10 A 2.5 mm² 4.0 mm² 6.0 mm² 10 mm² 16 mm²
20 A 4.0 mm² 10 mm² 16 mm² 25 mm² 35 mm²
48 V system
10 A 1.0 mm² 1.0 mm² 1.5 mm² 2.5 mm² 4.0 mm²
25 A 1.5 mm² 2.5 mm² 4.0 mm² 6.0 mm² 10 mm²
50 A 4.0 mm² 6.0 mm² 10 mm² 16 mm² 25 mm²
230 V string
5 A 1.0 mm² 1.0 mm² 1.0 mm² 1.0 mm² 1.5 mm²
10 A 1.0 mm² 1.0 mm² 1.5 mm² 2.5 mm² 4.0 mm²

Minimum cable for PV array wiring: 4 mm² H1Z2Z2-K (EU) or 10 AWG USE-2/PV (US) is the common minimum for panel strings regardless of drop calculation.

NEC 690.8 sizing for PV circuits

NEC Article 690 applies multipliers to the array’s short-circuit current (Isc) before sizing conductors and overcurrent protection. For a string with one panel having Isc = 10 A:

Step Factor Current
Panel Isc (nameplate) — 10 A
× 1.25 (NEC 690.8(A)(1)) × 1.25 12.5 A
× 1.25 (continuous load factor) × 1.25 15.6 A
Minimum conductor ampacity — ≥ 15.6 A

The first 1.25 multiplier accounts for the irradiance exceeding STC conditions (up to 1,250 W/m² in some climates). The second 1.25 is the continuous load rule. This double multiplication means PV string wiring is typically sized 2–3× the nameplate Isc.

Worked example: battery-to-inverter cable on a 48 V system

A 48 V, 3,000 W inverter draws 3,000 / (48 × 0.9) = 69.4 A DC at full load. Cable run is 2 m one-way.

Voltage drop (2%): Area = 2 × 2 × 69.4 × 0.017241 / (48 × 0.02) = 4.97 mm². Use 6 mm² (next size up).

Actual drop: V = 2 × 2 × 69.4 × 0.017241 / 6 = 0.80 V = 1.67 % of 48 V. ✓

Ampacity check: 6 mm² flexible copper in free air: typically rated 54–63 A. At 69.4 A continuous this is marginal. Use 10 mm² for the ampacity check.

Final selection: 10 mm² (ampacity governs over voltage drop for this short, high-current run).

Cable types for solar DC applications

Cable type Standard Temperature Features
H1Z2Z2-K EN 50618 −40 °C to +90 °C UV resistant, flexible, EU standard for PV
USE-2 / PV Wire UL 4703 90 °C wet US standard for exposed PV array wiring
XLPE insulated Various 90 °C General purpose; check UV rating for exposed runs
Standard THHN UL 83 90 °C dry Not for direct sun exposure without conduit

Do not use standard THHN in exposed outdoor solar applications. Use PV-rated cable (H1Z2Z2-K or USE-2/PV) for panel-to-combiner and combiner-to-inverter runs outside conduit.

More Q&As

What drop percentage should I use for a PV string?

1–2 % is common for array wiring (panel to combiner to inverter). The loss is real power — a 2 % drop in a 5 kW array wastes 100 W continuously during peak sun. The payback calculation usually favours keeping string wiring under 1 % for central inverter systems.

Can I use a single cable for multiple parallel strings?

No — run separate cables for each string. Parallel strings with unequal cable lengths have unequal resistances, causing unequal current sharing. The string with longer (thinner) cable runs at higher current, overheating its cable. Use equal lengths per string and combine at the combiner box.

What is the minimum cable size for a solar installation in Europe?

The minimum for PV string wiring under EN 50618 and most installer guides is 4 mm² H1Z2Z2-K, regardless of the calculated drop result. Many manufacturers void inverter warranties if smaller cable is used.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.