Formulas
Three-phase: I = kW × 1000 / (√3 × V × PF)
For three-phase, V is the line-to-line voltage.
Worked example
A 10 kW three-phase motor load at 400 V and 0.8 power factor: I = 10 000 / (1.732 × 400 × 0.8) = 18.04 A. This is the load current. Conductor and breaker sizing add further factors that are covered on their own pages.
How to use the calculator
Enter the power in kW, the supply voltage, the power factor, and choose single-phase or three-phase. The result is the current in each line, in amps. The default values are a 10 kW three-phase load at 400 V and a power factor of 0.8.
For three-phase, enter the line-to-line voltage, the one measured between any two phase conductors. Common values are 400 V, 415 V, 480 V and 690 V. For single-phase, use the voltage between the line and neutral, or between the two lines on a split-phase supply.
Quick reference examples
These are hand-calculated, and you can enter each one above to confirm:
- 5 kW, 230 V single-phase, PF 1: 5,000 / 230 = 21.7 A. This is a resistive heater.
- 10 kW, 230 V single-phase, PF 0.9: 10,000 / (230 × 0.9) = 48.3 A.
- 15 kW, 400 V three-phase, PF 0.85: 15,000 / (1.732 × 400 × 0.85) = 25.5 A.
- 75 kW, 480 V three-phase, PF 0.9: 75,000 / (1.732 × 480 × 0.9) = 100.2 A.
Power factor changes the answer a lot
The current is inversely proportional to power factor. The same 10 kW at 400 V three-phase draws 14.4 A at unity power factor but 18.0 A at 0.8. A low power factor means more current for the same useful work, which means larger cables, larger breakers and more loss in the supply. This is the reason utilities penalize poor power factor and why correction capacitors are fitted.
Motors: kW rating versus input power
A motor’s nameplate kW is normally the shaft output. The electrical input is higher by the efficiency. A 15 kW motor at 90% efficiency draws 16.7 kW from the supply, so use the input figure for the current. Many nameplates also list the rated current directly, and that value should be preferred over a calculated one.
The result is the running current at full load. Starting current on a direct-on-line induction motor is commonly five to eight times that value for a few seconds. Protection and cable selection have to allow for it, using the motor-circuit rules of the governing code.
What to do with the current
Full-load current is an input to the next step, not a final answer. Cable sizing needs the current plus derating for temperature, grouping and installation method. In the US, the overcurrent device for a continuous load is sized at 125% of the current, which the breaker size calculator handles.
Common mistakes
- Using the phase voltage with √3. Use 400 V with √3, or 230 V without it.
- Forgetting efficiency. Shaft kW understates the supply current.
- Assuming PF = 1. Only resistive loads reach it.
Questions
How many amps is 1 kW?
At 230 V single-phase and unity power factor, 4.35 A. At 400 V three-phase and a power factor of 0.8, 1.8 A.
How do I convert kW to amps at 120 V?
Divide watts by volts times power factor. 1 kW at 120 V, PF 1, is 8.33 A.
Is the result the same at 50 Hz and 60 Hz?
Yes. Frequency does not appear in the formula.
Should I use kW or kVA?
Use kW with a power factor, or kVA without one. The kVA to amps calculator covers the second.
kW to amps reference table
At power factor 1.0 for all entries. For inductive loads divide by the actual power factor — a 10 kW motor at 0.85 draws 10 / 0.85 = 11.76 kW equivalent, or use the formula directly.
| Power (kW) | 120 V 1-ph | 230 V 1-ph | 240 V 1-ph | 400 V 3-ph | 480 V 3-ph |
|---|---|---|---|---|---|
| 1 | 8.33 A | 4.35 A | 4.17 A | 1.44 A | 1.20 A |
| 2 | 16.7 A | 8.70 A | 8.33 A | 2.89 A | 2.41 A |
| 5 | 41.7 A | 21.7 A | 20.8 A | 7.22 A | 6.01 A |
| 10 | 83.3 A | 43.5 A | 41.7 A | 14.4 A | 12.0 A |
| 15 | — | 65.2 A | 62.5 A | 21.7 A | 18.0 A |
| 20 | — | 87.0 A | 83.3 A | 28.9 A | 24.1 A |
| 30 | — | — | — | 43.3 A | 36.1 A |
| 50 | — | — | — | 72.2 A | 60.1 A |
| 75 | — | — | — | 108 A | 90.2 A |
| 100 | — | — | — | 144 A | 120 A |
From kW to a complete circuit
Converting kW to amps is the first step. Under the NEC, sizing a circuit from kW alone is not the end — several further checks apply. The sequence:
- Calculate the running current: use the formula above. For a motor, use input kW (shaft kW divided by efficiency), or better, the nameplate amps.
- Apply the continuous-load multiplier: a load that runs three hours or more is a continuous load under NEC 210.20(A). Multiply running current by 1.25 to get the minimum circuit rating.
- Select the overcurrent device: round up to the next standard breaker size in NEC 240.6(A) — 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 A. The breaker size calculator does this step.
- Select the conductor: ampacity from NEC Table 310.12 must equal or exceed the breaker size. 10 AWG copper at 75 °C covers 35 A, 8 AWG covers 50 A, 6 AWG covers 65 A.
- Check voltage drop: for runs over 50 ft, check that the drop stays under 3 % at the breaker rating. Use the voltage drop calculator.
Worked example — 7.5 kW pump, 480 V three-phase, PF 0.85:
Running current: 7,500 / (1.732 × 480 × 0.85) = 10.6 A. Continuous-load multiplier: 10.6 × 1.25 = 13.25 A. Breaker: 15 A (next standard above 13.25). Conductor: 14 AWG at 75 °C covers 15 A — acceptable. For a 100 ft run: loop = 200 ft, 14 AWG resistance = 3.07 Ω/1,000 ft × 0.2 = 0.614 Ω, voltage drop = 10.6 × 0.614 = 6.5 V = 1.4 % — within the 3 % limit.
How voltage affects cable size for the same kW
Higher voltage means less current for the same power. That is the reason three-phase and 480 V distribution exists in industrial buildings: a 100 kW load draws 833 A at 120 V but only 139 A at 480 V three-phase, and the cable for 139 A costs far less.
| Load (kW) | 120 V 1-ph | 240 V 1-ph | 208 V 3-ph | 480 V 3-ph |
|---|---|---|---|---|
| 10 | 83.3 A | 41.7 A | 32.8 A | 14.1 A |
| 50 | 417 A | 208 A | 164 A | 70.6 A |
| 100 | — | 417 A | 328 A | 141 A |
PF = 1.0 for simplicity. The 480 V result is about 1/6 of the 120 V result — the economic argument for high-voltage distribution on larger sites.
More Q&As
How many amps is 5 kW at 240 V single-phase?
5,000 / 240 = 20.8 A for a resistive load. At a power factor of 0.9: 5,000 / (240 × 0.9) = 23.1 A.
How many amps is a 15 kW three-phase load at 415 V?
15,000 / (1.732 × 415 × 1.0) = 20.9 A at unity power factor. At PF 0.85: 20.9 / 0.85 = 24.6 A.
Why does the kW to amps formula use √3 for three-phase?
Line-to-line voltage is √3 times phase voltage in a star system. Power equals three times the per-phase power: 3 × V_phase × I × PF = √3 × V_line × I × PF.
What is the current for 1 kW on a 12 V DC system?
1,000 / 12 = 83.3 A. Low-voltage DC systems carry large currents for even modest loads, which is why cable sizing is critical for solar, RV and marine applications.