Amps measure current. Watts measure power. You can’t convert one to the other from the current alone, because power also depends on voltage and, for AC, on how much of the current does useful work. That is why the calculator asks for volts and, on AC, a power factor.
Formulas
AC single-phase: P = V × I × PF
AC three-phase: P = √3 × VLL × I × PF
P is real power in watts, V is voltage, I is current in amps, and PF is power factor between 0 and 1. For three-phase, VLL is the line-to-line voltage, the one you measure between any two phases, and I is the current in each line. The calculator assumes a balanced load.
Worked example
A single-phase 120 V circuit carries 15 A at a power factor of 0.9.
P = 120 × 15 × 0.9 = 1,620 W, or 1.62 kW.
Now the same current on a 400 V three-phase supply at 0.8 power factor, 10 A per line:
P = 1.732 × 400 × 10 × 0.8 = 5,543 W, or 5.54 kW.
You can enter both sets of numbers above and compare.
What power factor to use
For resistive loads like heaters and incandescent lamps, use 1. Induction motors typically run at 0.8 to 0.9 near full load and much lower when lightly loaded. Switch-mode power supplies and drives vary widely, so use the nameplate or the measured value. If you don’t know it, measure it or take it from the nameplate rather than guessing, because the wattage scales directly with it. To go the other way and find the current for a known power, use the kW to amps calculator.
Quick reference examples
- DC: 5 A at 24 V is 5 × 24 = 120 W.
- Single-phase, resistive: 10 A at 230 V and PF 1 is 2,300 W.
- Three-phase motor: 25 A at 400 V and PF 0.85 is 1.732 × 400 × 25 × 0.85 = 14,722 W.
Watts versus watt-hours
Watts are an instantaneous rate. Energy is watts multiplied by time, so a 1,620 W load running for two hours uses 3,240 Wh, or 3.24 kWh. This is the figure on an electricity bill. For battery runtime, divide the battery’s usable watt-hours by the load in watts.
Reading an appliance label
Labels give power in different ways. If the label shows watts, use that figure for the real power. If it shows only amps and volts, multiplying them gives volt-amps, which is the upper limit of the real power. The two are equal only when the power factor is 1. The same applies to a breaker or a socket: its amp rating limits the current, so the watts it can supply grow with the voltage, which is why 230 V circuits deliver almost twice the power of 120 V circuits on the same cable.
Common mistakes
- Using the wrong voltage on three-phase. Using the line-to-neutral voltage (for example 230 V) with the √3 formula understates power by a factor of 1.732. Use 400 V with √3, or use three times 230 V × I × PF.
- Treating apparent power as real power. Volt-amps (VA) and watts only match at a power factor of 1. A UPS rated 1,000 VA may deliver 600 to 900 W.
- Ignoring DC. On DC there is no power factor. Choose DC in the supply menu and the field is hidden.
Questions
How many watts is 1 amp?
It depends on voltage. At 120 V it is 120 W for a resistive load, at 230 V it is 230 W, and at 12 V DC it is 12 W.
Is amps to watts the same as amps to VA?
Not on AC. VA is V × I with no power factor. Watts include the power factor. On DC and for purely resistive loads they are equal.
Does this work for a motor?
Yes for the electrical input power, using the motor’s power factor. It does not give shaft output power, which is lower by the motor’s efficiency.
Can I use this for a battery?
Yes, choose DC. Watts are volts times amps at that instant, and watt-hours need the runtime as well.
Amps to watts reference table
At power factor 1.0. For inductive loads, multiply watts by the power factor — at PF 0.85 the actual watts are 85 % of the PF 1.0 column.
| Amps | 12 V DC | 24 V DC | 120 V | 230 V | 240 V | 400 V 3-ph |
|---|---|---|---|---|---|---|
| 1 A | 12 W | 24 W | 120 W | 230 W | 240 W | 693 W |
| 5 A | 60 W | 120 W | 600 W | 1,150 W | 1,200 W | 3,464 W |
| 10 A | 120 W | 240 W | 1,200 W | 2,300 W | 2,400 W | 6,928 W |
| 15 A | 180 W | 360 W | 1,800 W | 3,450 W | 3,600 W | 10,392 W |
| 20 A | 240 W | 480 W | 2,400 W | 4,600 W | 4,800 W | 13,856 W |
| 30 A | 360 W | 720 W | 3,600 W | 6,900 W | 7,200 W | 20,784 W |
Three-phase values are √3 × V × I.
From watts to circuit sizing
Once you have watts, the next step is sizing or evaluating the circuit. Under the NEC:
- Check if the load is continuous. A load that runs three hours or more is a continuous load. A 1,800 W heater drawing 15 A on 120 V is continuous; the minimum breaker is 15 × 1.25 = 18.75 A, so a 20 A breaker. Use the breaker size calculator.
- Check voltage drop. For long runs, cable resistance wastes some watts as heat. At 15 A through 100 ft of 12 AWG copper (resistance = 0.614 Ω round-trip), the loss is 15² × 0.614 = 138 W, about 7.6 % of 1,800 W — too high. Use 10 AWG for a long, high-current run.
- Check energy cost. Watts × hours = watt-hours. The 1,800 W heater running 8 hours uses 14.4 kWh.
DC voltage and cable size
On a DC system, P = V × I with no power factor. The same 1,200 W drawn at 12 V requires 100 A, while at 48 V it’s only 25 A. Higher DC voltage means smaller cables for the same power — the reason 48 V is now standard for larger off-grid systems.
| Power (W) | 12 V current | 24 V current | 48 V current |
|---|---|---|---|
| 300 W | 25.0 A | 12.5 A | 6.25 A |
| 600 W | 50.0 A | 25.0 A | 12.5 A |
| 1,200 W | 100 A | 50.0 A | 25.0 A |
| 2,400 W | 200 A | 100 A | 50.0 A |
A 100 A cable run from a 12 V battery to an inverter needs very heavy cable for even a short distance. Moving to 48 V reduces the cable cost by 4× on the same run.
Watts versus VA: reading labels correctly
Appliances and circuit equipment sometimes use watts and VA interchangeably, which causes errors:
- Watts (W) = real power. A resistive heater rated “2,000 W” draws exactly 2,000 W.
- Volt-amps (VA) = apparent power = V × I, with no power factor adjustment. A UPS rated “1,000 VA” may supply only 600–900 W of real power.
- What matters for circuit sizing is the current, which comes from VA, not from watts. A 1,000 VA UPS at 120 V draws 1,000 / 120 = 8.33 A from the wall — that is what the breaker and cable must handle, not the lower 900 W figure.
For motors the nameplate lists the rated current directly. Use that for circuit sizing, not a figure calculated from shaft watts.
More Q&As
How many watts can a 20 A, 240 V circuit carry continuously?
Maximum: 20 × 240 = 4,800 W at PF 1. For a continuous load, 80 % of that is 3,840 W (the NEC 125 % rule limits continuous loads to 80 % of breaker rating).
How many watts does a 15 A, 120 V circuit support continuously?
15 × 120 = 1,800 W maximum. For a continuous load: 1,800 × 0.8 = 1,440 W.
Why does three-phase have √3 in the formula?
Three-phase delivers power through three conductors 120° apart. The combined power is √3 × V_line × I × PF, not 3 × V_line × I, because the phases partly overlap — their vector sum is √3 times, not 3 times, the per-phase value.
How do I find watts from a clamp meter reading?
Measure amps and volts separately on the same conductor. For single-phase: W ≈ V × I × PF. If the load is resistive, PF ≈ 1 and watts ≈ V × I. For an accurate reading on inductive loads, use a watt-meter or a clamp meter that measures both simultaneously.
Related calculators
Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.