This chart gives the line current for loads from 0.5 to 2,000 kW. Single-phase values assume a power factor of 1.0, which suits heaters and other resistive loads. Three-phase values assume 0.9, a common figure for a mix of motors and electronics. If your power factor is different, the correction is one multiplication, shown below.
| kW | 120 V | 208 V | 230 V | 240 V |
|---|---|---|---|---|
| 0.5 | 4.17 | 2.40 | 2.17 | 2.08 |
| 1 | 8.33 | 4.81 | 4.35 | 4.17 |
| 1.5 | 12.5 | 7.21 | 6.52 | 6.25 |
| 2 | 16.7 | 9.62 | 8.70 | 8.33 |
| 2.2 | 18.3 | 10.6 | 9.57 | 9.17 |
| 3 | 25.0 | 14.4 | 13.0 | 12.5 |
| 3.7 | 30.8 | 17.8 | 16.1 | 15.4 |
| 4 | 33.3 | 19.2 | 17.4 | 16.7 |
| 5 | 41.7 | 24.0 | 21.7 | 20.8 |
| 5.5 | 45.8 | 26.4 | 23.9 | 22.9 |
| 5.9 | 49.2 | 28.4 | 25.7 | 24.6 |
| 6 | 50.0 | 28.8 | 26.1 | 25.0 |
| 7.2 | 60.0 | 34.6 | 31.3 | 30.0 |
| 7.5 | 62.5 | 36.1 | 32.6 | 31.3 |
| 7.6 | 63.3 | 36.5 | 33.0 | 31.7 |
| 8 | 66.7 | 38.5 | 34.8 | 33.3 |
| 9 | 75.0 | 43.3 | 39.1 | 37.5 |
| 10 | 83.3 | 48.1 | 43.5 | 41.7 |
| 11 | 91.7 | 52.9 | 47.8 | 45.8 |
| 12 | 100 | 57.7 | 52.2 | 50.0 |
| 15 | 125 | 72.1 | 65.2 | 62.5 |
| 18.5 | 154 | 88.9 | 80.4 | 77.1 |
| 20 | 167 | 96.2 | 87.0 | 83.3 |
| 22 | 183 | 106 | 95.7 | 91.7 |
| 25 | 208 | 120 | 109 | 104 |
| 30 | 250 | 144 | 130 | 125 |
| 37 | 308 | 178 | 161 | 154 |
| 40 | 333 | 192 | 174 | 167 |
| 45 | 375 | 216 | 196 | 188 |
| 50 | 417 | 240 | 217 | 208 |
| 55 | 458 | 264 | 239 | 229 |
| 75 | 625 | 361 | 326 | 313 |
| 90 | 750 | 433 | 391 | 375 |
| 100 | 833 | 481 | 435 | 417 |
| 150 | 1,250 | 721 | 652 | 625 |
| 200 | 1,667 | 962 | 870 | 833 |
| 250 | 2,083 | 1,202 | 1,087 | 1,042 |
| 300 | 2,500 | 1,442 | 1,304 | 1,250 |
| 350 | 2,917 | 1,683 | 1,522 | 1,458 |
| 400 | 3,333 | 1,923 | 1,739 | 1,667 |
| 500 | 4,167 | 2,404 | 2,174 | 2,083 |
| 750 | 6,250 | 3,606 | 3,261 | 3,125 |
| 1000 | 8,333 | 4,808 | 4,348 | 4,167 |
| 1500 | 12,500 | 7,212 | 6,522 | 6,250 |
| 2000 | 16,667 | 9,615 | 8,696 | 8,333 |
| kW | 208 V | 240 V | 400 V | 480 V | 600 V |
|---|---|---|---|---|---|
| 0.5 | 1.54 | 1.34 | 0.80 | 0.67 | 0.53 |
| 1 | 3.08 | 2.67 | 1.60 | 1.34 | 1.07 |
| 1.5 | 4.63 | 4.01 | 2.41 | 2.00 | 1.60 |
| 2 | 6.17 | 5.35 | 3.21 | 2.67 | 2.14 |
| 2.2 | 6.79 | 5.88 | 3.53 | 2.94 | 2.35 |
| 3 | 9.25 | 8.02 | 4.81 | 4.01 | 3.21 |
| 3.7 | 11.4 | 9.89 | 5.93 | 4.94 | 3.96 |
| 4 | 12.3 | 10.7 | 6.42 | 5.35 | 4.28 |
| 5 | 15.4 | 13.4 | 8.02 | 6.68 | 5.35 |
| 5.5 | 17.0 | 14.7 | 8.82 | 7.35 | 5.88 |
| 5.9 | 18.2 | 15.8 | 9.46 | 7.89 | 6.31 |
| 6 | 18.5 | 16.0 | 9.62 | 8.02 | 6.42 |
| 7.2 | 22.2 | 19.2 | 11.5 | 9.62 | 7.70 |
| 7.5 | 23.1 | 20.0 | 12.0 | 10.0 | 8.02 |
| 7.6 | 23.4 | 20.3 | 12.2 | 10.2 | 8.13 |
| 8 | 24.7 | 21.4 | 12.8 | 10.7 | 8.55 |
| 9 | 27.8 | 24.1 | 14.4 | 12.0 | 9.62 |
| 10 | 30.8 | 26.7 | 16.0 | 13.4 | 10.7 |
| 11 | 33.9 | 29.4 | 17.6 | 14.7 | 11.8 |
| 12 | 37.0 | 32.1 | 19.2 | 16.0 | 12.8 |
| 15 | 46.3 | 40.1 | 24.1 | 20.0 | 16.0 |
| 18.5 | 57.1 | 49.4 | 29.7 | 24.7 | 19.8 |
| 20 | 61.7 | 53.5 | 32.1 | 26.7 | 21.4 |
| 22 | 67.9 | 58.8 | 35.3 | 29.4 | 23.5 |
| 25 | 77.1 | 66.8 | 40.1 | 33.4 | 26.7 |
| 30 | 92.5 | 80.2 | 48.1 | 40.1 | 32.1 |
| 37 | 114 | 98.9 | 59.3 | 49.4 | 39.6 |
| 40 | 123 | 107 | 64.2 | 53.5 | 42.8 |
| 45 | 139 | 120 | 72.2 | 60.1 | 48.1 |
| 50 | 154 | 134 | 80.2 | 66.8 | 53.5 |
| 55 | 170 | 147 | 88.2 | 73.5 | 58.8 |
| 75 | 231 | 200 | 120 | 100 | 80.2 |
| 90 | 278 | 241 | 144 | 120 | 96.2 |
| 100 | 308 | 267 | 160 | 134 | 107 |
| 150 | 463 | 401 | 241 | 200 | 160 |
| 200 | 617 | 535 | 321 | 267 | 214 |
| 250 | 771 | 668 | 401 | 334 | 267 |
| 300 | 925 | 802 | 481 | 401 | 321 |
| 350 | 1,079 | 936 | 561 | 468 | 374 |
| 400 | 1,234 | 1,069 | 642 | 535 | 428 |
| 500 | 1,542 | 1,336 | 802 | 668 | 535 |
| 750 | 2,313 | 2,005 | 1,203 | 1,002 | 802 |
| 1000 | 3,084 | 2,673 | 1,604 | 1,336 | 1,069 |
| 1500 | 4,626 | 4,009 | 2,406 | 2,005 | 1,604 |
| 2000 | 6,168 | 5,346 | 3,208 | 2,673 | 2,138 |
The formulas
Three-phase: I = P × 1000 / (√3 × VLL × PF)
P is the real power in kW, V the voltage and PF the power factor. For three-phase, VLL is the line-to-line voltage, such as 208, 400, 480 or 600 V, and the result is the current in each line. For anything not in the chart, the kW to amps calculator takes any value.
Worked example
A 22 kW three-phase load at 400 V and a power factor of 0.9 draws 35.3 A, the 22 kW row. An EV charger of 7.6 kW on a 240 V single-phase supply draws 31.7 A.
A 25 kW three-phase load at 480 V and a power factor of 0.9. The chart gives 33.4 A. If the power factor is 0.8, multiply by 0.9 / 0.8 = 1.125, which gives 37.6 A. Direct calculation agrees: 25,000 / (1.732 × 480 × 0.8) = 37.6 A.
Current scales in a straight line with power, so you can add rows. A 35 kW load at 480 V and PF 0.9 is the 25 kW row plus the 10 kW row: 33.4 + 13.4 = 46.8 A.
Before you use the number for sizing
- Line current is not the design current. A continuous load, one that runs for three hours or more, needs 125 % of its current when you choose the breaker. See how to size a circuit breaker.
- Motors are different. The NEC sizes motor circuits from table full-load current, not from kW. Use the HP to amps calculator for motors.
- A kW rating may be shaft power. On a motor nameplate, kW is usually the mechanical output. The electrical input is higher by the efficiency.
Questions
How many amps is 10 kW?
At 240 V single-phase and PF 1.0, 41.7 A. At 480 V three-phase and PF 0.9, 13.4 A. Higher voltage means less current for the same power, which is why large loads use three-phase at 480 V.
Why is the 208 V three-phase current higher than at 240 V?
Current is power divided by voltage, so a lower voltage needs more current for the same kW. A 30 kW load draws 92.5 A at 208 V and 80.2 A at 240 V.
How many amps is 7.6 kW?
31.7 A at 240 V single-phase and PF 1.0, or 63.3 A at 120 V. The 7.6 kW row is a common size for a home EV charger.
How many amps is 5.9 kW?
24.6 A at 240 V single-phase and PF 1.0, or 49.2 A at 120 V.
How many amps is 150 kW?
At 480 V three-phase and PF 0.9, 200 A. At 400 V it is 241 A, and at 208 V it is 463 A.
Which power factor should I use?
Use the figure from the equipment data or measurements. Resistive heaters are 1.0, lightly loaded motors can be 0.6 or below, and 0.8 to 0.9 is a usual planning value.
Common load reference — kW and amps
Typical running current for common loads at standard voltages:
| Load | kW | 120 V single-phase | 240 V single-phase | 480 V three-phase |
|---|---|---|---|---|
| LED lighting circuit | 1.0 kW | 8.3 A | 4.2 A | — |
| Microwave / small heater | 1.2 kW | 10.0 A | 5.0 A | — |
| Level 1 EV charger | 1.44 kW | 12.0 A | 6.0 A | — |
| Level 2 EV charger | 7.6 kW | — | 31.7 A | — |
| Water heater element | 4.5 kW | — | 18.75 A | — |
| 3-ton heat pump (running) | 3.5 kW | — | 14.6 A | — |
| 5 hp motor | 3.73 kW | — | — | 4.5 A |
| 10 hp motor | 7.46 kW | — | — | 9.0 A |
| 25 hp motor | 18.65 kW | — | — | 22.5 A |
| 50 hp motor | 37.3 kW | — | — | 45.1 A |
Motor currents above are for typical 460 V motors at PF 0.90, efficiency 92%. For NEC sizing use Table 430.250 values, not these calculated figures.
Three-phase vs single-phase: why it matters for sizing
The same 10 kW load draws very different currents depending on supply:
| Supply | Voltage | Current | Cable cross-section |
|---|---|---|---|
| Single-phase | 120 V | 83.3 A | Very large |
| Single-phase | 240 V | 41.7 A | Large |
| Three-phase | 208 V | 27.6 A | Medium |
| Three-phase | 480 V | 13.4 A | Small |
| Three-phase | 600 V | 10.7 A | Smaller |
Three-phase at high voltage reduces current by 5–8× compared to single-phase 120 V, which is why large industrial loads run at 480 V three-phase: smaller conductors, smaller conduit, lower voltage drop, and reduced I²R losses.
Continuous load rule and breaker sizing
The amps from this chart are running currents, not breaker sizes. For a continuous load (operates for 3 hours or more), NEC 210.20(A) requires the breaker to be rated at least 125% of the load current:
| Load | Running amps | Minimum breaker (125%) |
|---|---|---|
| 10 kW at 240 V single-phase | 41.7 A | 52.1 A → 60 A breaker |
| 20 kW at 480 V three-phase | 26.8 A | 33.5 A → 40 A breaker |
| 50 kW at 480 V three-phase | 67.1 A | 83.9 A → 90 A breaker |
| 100 kW at 480 V three-phase | 134 A | 167.5 A → 175 A breaker |
Standard breaker sizes (NEC 240.6(A)): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A.
More Q&As
How do I convert kVA to amps using this chart?
If the load’s power factor is known: kW = kVA × PF, then use the chart. Without knowing PF, divide by the system voltage and √3 for three-phase directly: I = kVA × 1000 / (√3 × V) for three-phase, I = kVA × 1000 / V for single-phase.
Why does current drop with higher voltage for the same kW?
Power = Voltage × Current, so for fixed power, current and voltage are inversely proportional. This is why transmission lines run at 115–765 kV — the same megawatts require milliamps, not kiloamps, drastically reducing resistive losses and conductor size.
How many amps is a 400 kW generator at 400 V three-phase?
I = 400,000 / (1.732 × 400 × 0.9) = 641 A. For a generator operating at 0.8 PF (generator nameplate convention): I = 400,000 / (1.732 × 400 × 0.8) = 722 A. Always check the generator’s nameplate PF rating.