Chart

kW to Amps Chart

kW to amps for 120 to 600 V, including 230 V and 400 V, single-phase and three-phase, with the formulas and a worked example for other power factors.

Updated 2026-11-23

ElectricalFree, no sign-upWorked examples

This chart gives the line current for loads from 0.5 to 2,000 kW. Single-phase values assume a power factor of 1.0, which suits heaters and other resistive loads. Three-phase values assume 0.9, a common figure for a mix of motors and electronics. If your power factor is different, the correction is one multiplication, shown below.

Single-phase line current in amps, power factor 1.0
kW120 V208 V230 V240 V
0.54.172.402.172.08
18.334.814.354.17
1.512.57.216.526.25
216.79.628.708.33
2.218.310.69.579.17
325.014.413.012.5
3.730.817.816.115.4
433.319.217.416.7
541.724.021.720.8
5.545.826.423.922.9
5.949.228.425.724.6
650.028.826.125.0
7.260.034.631.330.0
7.562.536.132.631.3
7.663.336.533.031.7
866.738.534.833.3
975.043.339.137.5
1083.348.143.541.7
1191.752.947.845.8
1210057.752.250.0
1512572.165.262.5
18.515488.980.477.1
2016796.287.083.3
2218310695.791.7
25208120109104
30250144130125
37308178161154
40333192174167
45375216196188
50417240217208
55458264239229
75625361326313
90750433391375
100833481435417
1501,250721652625
2001,667962870833
2502,0831,2021,0871,042
3002,5001,4421,3041,250
3502,9171,6831,5221,458
4003,3331,9231,7391,667
5004,1672,4042,1742,083
7506,2503,6063,2613,125
10008,3334,8084,3484,167
150012,5007,2126,5226,250
200016,6679,6158,6968,333
Three-phase line current in amps, power factor 0.9
kW208 V240 V400 V480 V600 V
0.51.541.340.800.670.53
13.082.671.601.341.07
1.54.634.012.412.001.60
26.175.353.212.672.14
2.26.795.883.532.942.35
39.258.024.814.013.21
3.711.49.895.934.943.96
412.310.76.425.354.28
515.413.48.026.685.35
5.517.014.78.827.355.88
5.918.215.89.467.896.31
618.516.09.628.026.42
7.222.219.211.59.627.70
7.523.120.012.010.08.02
7.623.420.312.210.28.13
824.721.412.810.78.55
927.824.114.412.09.62
1030.826.716.013.410.7
1133.929.417.614.711.8
1237.032.119.216.012.8
1546.340.124.120.016.0
18.557.149.429.724.719.8
2061.753.532.126.721.4
2267.958.835.329.423.5
2577.166.840.133.426.7
3092.580.248.140.132.1
3711498.959.349.439.6
4012310764.253.542.8
4513912072.260.148.1
5015413480.266.853.5
5517014788.273.558.8
7523120012010080.2
9027824114412096.2
100308267160134107
150463401241200160
200617535321267214
250771668401334267
300925802481401321
3501,079936561468374
4001,2341,069642535428
5001,5421,336802668535
7502,3132,0051,2031,002802
10003,0842,6731,6041,3361,069
15004,6264,0092,4062,0051,604
20006,1685,3463,2082,6732,138

The formulas

Single-phase: I = P × 1000 / (V × PF)
Three-phase: I = P × 1000 / (√3 × VLL × PF)

P is the real power in kW, V the voltage and PF the power factor. For three-phase, VLL is the line-to-line voltage, such as 208, 400, 480 or 600 V, and the result is the current in each line. For anything not in the chart, the kW to amps calculator takes any value.

Worked example

A 22 kW three-phase load at 400 V and a power factor of 0.9 draws 35.3 A, the 22 kW row. An EV charger of 7.6 kW on a 240 V single-phase supply draws 31.7 A.

A 25 kW three-phase load at 480 V and a power factor of 0.9. The chart gives 33.4 A. If the power factor is 0.8, multiply by 0.9 / 0.8 = 1.125, which gives 37.6 A. Direct calculation agrees: 25,000 / (1.732 × 480 × 0.8) = 37.6 A.

Current scales in a straight line with power, so you can add rows. A 35 kW load at 480 V and PF 0.9 is the 25 kW row plus the 10 kW row: 33.4 + 13.4 = 46.8 A.

Before you use the number for sizing

Questions

How many amps is 10 kW?

At 240 V single-phase and PF 1.0, 41.7 A. At 480 V three-phase and PF 0.9, 13.4 A. Higher voltage means less current for the same power, which is why large loads use three-phase at 480 V.

Why is the 208 V three-phase current higher than at 240 V?

Current is power divided by voltage, so a lower voltage needs more current for the same kW. A 30 kW load draws 92.5 A at 208 V and 80.2 A at 240 V.

How many amps is 7.6 kW?

31.7 A at 240 V single-phase and PF 1.0, or 63.3 A at 120 V. The 7.6 kW row is a common size for a home EV charger.

How many amps is 5.9 kW?

24.6 A at 240 V single-phase and PF 1.0, or 49.2 A at 120 V.

How many amps is 150 kW?

At 480 V three-phase and PF 0.9, 200 A. At 400 V it is 241 A, and at 208 V it is 463 A.

Which power factor should I use?

Use the figure from the equipment data or measurements. Resistive heaters are 1.0, lightly loaded motors can be 0.6 or below, and 0.8 to 0.9 is a usual planning value.

Common load reference — kW and amps

Typical running current for common loads at standard voltages:

Load kW 120 V single-phase 240 V single-phase 480 V three-phase
LED lighting circuit 1.0 kW 8.3 A 4.2 A —
Microwave / small heater 1.2 kW 10.0 A 5.0 A —
Level 1 EV charger 1.44 kW 12.0 A 6.0 A —
Level 2 EV charger 7.6 kW — 31.7 A —
Water heater element 4.5 kW — 18.75 A —
3-ton heat pump (running) 3.5 kW — 14.6 A —
5 hp motor 3.73 kW — — 4.5 A
10 hp motor 7.46 kW — — 9.0 A
25 hp motor 18.65 kW — — 22.5 A
50 hp motor 37.3 kW — — 45.1 A

Motor currents above are for typical 460 V motors at PF 0.90, efficiency 92%. For NEC sizing use Table 430.250 values, not these calculated figures.

Three-phase vs single-phase: why it matters for sizing

The same 10 kW load draws very different currents depending on supply:

Supply Voltage Current Cable cross-section
Single-phase 120 V 83.3 A Very large
Single-phase 240 V 41.7 A Large
Three-phase 208 V 27.6 A Medium
Three-phase 480 V 13.4 A Small
Three-phase 600 V 10.7 A Smaller

Three-phase at high voltage reduces current by 5–8× compared to single-phase 120 V, which is why large industrial loads run at 480 V three-phase: smaller conductors, smaller conduit, lower voltage drop, and reduced I²R losses.

Continuous load rule and breaker sizing

The amps from this chart are running currents, not breaker sizes. For a continuous load (operates for 3 hours or more), NEC 210.20(A) requires the breaker to be rated at least 125% of the load current:

Load Running amps Minimum breaker (125%)
10 kW at 240 V single-phase 41.7 A 52.1 A → 60 A breaker
20 kW at 480 V three-phase 26.8 A 33.5 A → 40 A breaker
50 kW at 480 V three-phase 67.1 A 83.9 A → 90 A breaker
100 kW at 480 V three-phase 134 A 167.5 A → 175 A breaker

Standard breaker sizes (NEC 240.6(A)): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A.

More Q&As

How do I convert kVA to amps using this chart?

If the load’s power factor is known: kW = kVA × PF, then use the chart. Without knowing PF, divide by the system voltage and √3 for three-phase directly: I = kVA × 1000 / (√3 × V) for three-phase, I = kVA × 1000 / V for single-phase.

Why does current drop with higher voltage for the same kW?

Power = Voltage × Current, so for fixed power, current and voltage are inversely proportional. This is why transmission lines run at 115–765 kV — the same megawatts require milliamps, not kiloamps, drastically reducing resistive losses and conductor size.

How many amps is a 400 kW generator at 400 V three-phase?

I = 400,000 / (1.732 × 400 × 0.9) = 641 A. For a generator operating at 0.8 PF (generator nameplate convention): I = 400,000 / (1.732 × 400 × 0.8) = 722 A. Always check the generator’s nameplate PF rating.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.