Short answer: kW = kVA × power factor. At 0.8 power factor 1 kVA is 0.8 kW, at 0.9 it is 0.9 kW, and at a power factor of 1 they are equal. The tables below cover common ratings and power factors.
kVA is apparent power, the total the supply must carry. kW is real power, the part that does useful work. The ratio between them is the power factor. Transformers, generators and UPS units are rated in kVA because their heating depends on current, and current does not care how much of it does useful work.
kVA to kW table
Find the kVA rating of the transformer, generator or UPS in the first column, then read across to the power factor of the load.
| kVA | PF 0.7 | PF 0.8 | PF 0.85 | PF 0.9 | PF 0.95 | PF 1 |
|---|---|---|---|---|---|---|
| 1 | 0.70 | 0.80 | 0.85 | 0.90 | 0.95 | 1.00 |
| 2 | 1.40 | 1.60 | 1.70 | 1.80 | 1.90 | 2.00 |
| 3 | 2.10 | 2.40 | 2.55 | 2.70 | 2.85 | 3.00 |
| 5 | 3.50 | 4.00 | 4.25 | 4.50 | 4.75 | 5.00 |
| 7.5 | 5.25 | 6.00 | 6.38 | 6.75 | 7.13 | 7.50 |
| 10 | 7.00 | 8.00 | 8.50 | 9.00 | 9.50 | 10.0 |
| 15 | 10.5 | 12.0 | 12.8 | 13.5 | 14.3 | 15.0 |
| 20 | 14.0 | 16.0 | 17.0 | 18.0 | 19.0 | 20.0 |
| 25 | 17.5 | 20.0 | 21.3 | 22.5 | 23.8 | 25.0 |
| 30 | 21.0 | 24.0 | 25.5 | 27.0 | 28.5 | 30.0 |
| 37.5 | 26.3 | 30.0 | 31.9 | 33.8 | 35.6 | 37.5 |
| 45 | 31.5 | 36.0 | 38.3 | 40.5 | 42.8 | 45.0 |
| 50 | 35.0 | 40.0 | 42.5 | 45.0 | 47.5 | 50.0 |
| 75 | 52.5 | 60.0 | 63.8 | 67.5 | 71.3 | 75.0 |
| 100 | 70.0 | 80.0 | 85.0 | 90.0 | 95.0 | 100 |
| 112.5 | 78.8 | 90.0 | 95.6 | 101 | 107 | 113 |
| 150 | 105 | 120 | 128 | 135 | 143 | 150 |
| 200 | 140 | 160 | 170 | 180 | 190 | 200 |
| 225 | 158 | 180 | 191 | 203 | 214 | 225 |
| 250 | 175 | 200 | 213 | 225 | 238 | 250 |
| 300 | 210 | 240 | 255 | 270 | 285 | 300 |
| 400 | 280 | 320 | 340 | 360 | 380 | 400 |
| 500 | 350 | 400 | 425 | 450 | 475 | 500 |
| 750 | 525 | 600 | 638 | 675 | 713 | 750 |
| 1000 | 700 | 800 | 850 | 900 | 950 | 1,000 |
| 1500 | 1,050 | 1,200 | 1,275 | 1,350 | 1,425 | 1,500 |
| 2000 | 1,400 | 1,600 | 1,700 | 1,800 | 1,900 | 2,000 |
kW to kVA table
To size equipment for a known real load, divide by the power factor. Read the kW load in the first column and the kVA rating it needs in the column for your power factor.
| kW | PF 0.7 | PF 0.8 | PF 0.85 | PF 0.9 | PF 0.95 | PF 1 |
|---|---|---|---|---|---|---|
| 1 | 1.43 | 1.25 | 1.18 | 1.11 | 1.05 | 1.00 |
| 2 | 2.86 | 2.50 | 2.35 | 2.22 | 2.11 | 2.00 |
| 5 | 7.14 | 6.25 | 5.88 | 5.56 | 5.26 | 5.00 |
| 10 | 14.3 | 12.5 | 11.8 | 11.1 | 10.5 | 10.0 |
| 15 | 21.4 | 18.8 | 17.6 | 16.7 | 15.8 | 15.0 |
| 20 | 28.6 | 25.0 | 23.5 | 22.2 | 21.1 | 20.0 |
| 25 | 35.7 | 31.3 | 29.4 | 27.8 | 26.3 | 25.0 |
| 30 | 42.9 | 37.5 | 35.3 | 33.3 | 31.6 | 30.0 |
| 40 | 57.1 | 50.0 | 47.1 | 44.4 | 42.1 | 40.0 |
| 50 | 71.4 | 62.5 | 58.8 | 55.6 | 52.6 | 50.0 |
| 60 | 85.7 | 75.0 | 70.6 | 66.7 | 63.2 | 60.0 |
| 75 | 107 | 93.8 | 88.2 | 83.3 | 78.9 | 75.0 |
| 80 | 114 | 100 | 94.1 | 88.9 | 84.2 | 80.0 |
| 100 | 143 | 125 | 118 | 111 | 105 | 100 |
| 150 | 214 | 188 | 176 | 167 | 158 | 150 |
| 200 | 286 | 250 | 235 | 222 | 211 | 200 |
| 250 | 357 | 313 | 294 | 278 | 263 | 250 |
| 300 | 429 | 375 | 353 | 333 | 316 | 300 |
| 400 | 571 | 500 | 471 | 444 | 421 | 400 |
| 500 | 714 | 625 | 588 | 556 | 526 | 500 |
| 800 | 1,143 | 1,000 | 941 | 889 | 842 | 800 |
| 1000 | 1,429 | 1,250 | 1,176 | 1,111 | 1,053 | 1,000 |
The same formula applies to single-phase and three-phase, because the √3 for three-phase is already in the kVA figure.
Formulas
kVA = kW / PF
kvar = √(kVA² − kW²)
PF is the power factor, between 0 and 1. The three quantities form a right triangle with kVA as the hypotenuse, which is why kVA is never smaller than kW. They are equal only at a power factor of 1.
Worked examples
A 100 kVA load at a power factor of 0.8:
kW = 100 × 0.8 = 80 kW, and kvar = √(100² − 80²) = 60 kvar.
A 45 kW load at 0.9 power factor:
kVA = 45 / 0.9 = 50 kVA, and kvar = √(50² − 45²) = 21.8 kvar.
More examples:
- A 500 kVA generator at 0.8 power factor delivers 500 × 0.8 = 400 kW. Look at the 500 kVA row, 0.8 column.
- A 250 kW load at 0.9 power factor needs 250 / 0.9 = 277.8 kVA. Choose the next standard rating above that, and use the generator size calculator if you are sizing a set.
- A 100 kVA transformer feeding motors at 0.85 can supply 100 × 0.85 = 85 kW of real load before it reaches its kVA limit.
Single-phase and three-phase
The conversion is the same. For example, a three-phase load drawing 100 A at 480 V is √3 × 480 × 100 / 1,000 = 83.1 kVA. At a power factor of 0.85 that is 83.1 × 0.85 = 70.7 kW. The kVA to amps calculator and the transformer full-load current chart give the current for a given kVA.
Typical power factors
- Resistive heaters and incandescent lamps: 1.0.
- Induction motors at full load: 0.8 to 0.9, and much lower when lightly loaded.
- LED drivers and modern switch-mode supplies: often 0.9 or better, but check the label.
- Generators: commonly rated at 0.8 power factor, so a 100 kVA set delivers 80 kW.
- Modern UPS units: many are rated at 0.9 or 1.0, so their kW can be close to the kVA figure.
What improving the power factor does
Take the 80 kW load above at a power factor of 0.8. It draws 100 kVA. If capacitors raise the power factor to 0.95, the same 80 kW needs only 80 / 0.95 = 84.2 kVA, a drop of about 16 % in apparent power and current. The reactive power falls from 60 kvar to 26.3 kvar, so about 33.7 kvar of capacitors are needed. The power factor correction calculator does this step.
Common mistakes
- Sizing a generator or transformer from kW alone. Divide by the power factor first. 80 kW at 0.8 needs 100 kVA, not 80.
- Treating kVA and kW as equal. They only match at unity power factor.
- Entering a power factor above 1. It cannot exceed 1. The calculator rejects it.
- Using one power factor for a mixed load. A site of motors and heaters has a combined power factor that is neither. Use the measured figure if you have it.
Questions
How many kW is 1 kVA?
At 0.8 power factor it is 0.8 kW, at 0.9 it is 0.9 kW and at 1.0 it is 1 kW.
Is the kVA to kW formula different for three-phase?
No. kW = kVA × PF for both. The three-phase √3 is already inside the kVA value, so only the current changes.
Is kVA bigger than kW?
kVA is always greater than or equal to kW. They are equal at a power factor of 1.
How many kW is 100 kVA?
At 0.8 power factor it is 80 kW, and at 0.9 it is 90 kW.
How do I convert kW to kVA at 0.85 power factor?
Divide by 0.85. For example, 50 kW is 50 / 0.85 = 58.8 kVA.
Why are transformers rated in kVA and not kW?
Their losses depend on the current they carry, not on the power factor of the load. A transformer rated in kVA can carry that current whatever the load does with it.
Related calculators
Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.