Transformer Full-Load Current Chart

Three-phase transformer full-load amps for 15 to 2,500 kVA at 208, 240, 480 and 600 V, plus 4,160, 12,470 and 13,800 V, with formula and example.

Updated 2026-11-19

Protection and MVFree, no sign-upWorked examples

The full-load current of a transformer is the current at its rated kVA. It sets the minimum size of conductors and overcurrent devices on each side. The tables cover standard three-phase sizes at the usual secondary voltages and at common primary voltages.

Three-phase full-load current in amps at 208 V, 240 V, 480 V, 600 V
kVA208 V240 V480 V600 V
1541.636.118.014.4
3083.372.236.128.9
4512510854.143.3
7520818090.272.2
112.5312271135108
150416361180144
225625541271217
300833722361289
5001,3881,203601481
7502,0821,804902722
10002,7762,4061,203962
15004,1643,6081,8041,443
20005,5514,8112,4061,925
25006,9396,0143,0072,406
Three-phase full-load current in amps at 4160 V, 12470 V, 13800 V
kVA4160 V12470 V13800 V
152.080.690.63
304.161.391.26
456.252.081.88
7510.43.473.14
112.515.65.214.71
15020.86.946.28
22531.210.49.41
30041.613.912.6
50069.423.120.9
75010434.731.4
100013946.341.8
150020869.462.8
200027892.683.7
2500347116105

The formula

I = kVA × 1000 / (√3 × VLL)

kVA is the rated apparent power and VLL the line-to-line voltage on the side you are checking. Full-load current is independent of the load power factor, because kVA already includes it. The transformer full-load current calculator gives both sides at once for any rating. For a single-phase unit, divide kVA × 1000 by the voltage.

Worked example

A 500 kVA transformer with a 480 V secondary has a full-load current of 500,000 / (1.732 × 480) = 601 A, matching the chart. The same transformer on a 208 V secondary has 1,388 A. The lower the voltage, the larger the bus, cable and breaker needed for the same kVA.

On a 13,800 V primary the same 500 kVA unit draws 20.9 A, so the primary side is a small cable and a modest fuse. This large ratio between sides is also why the primary and secondary protection are chosen separately.

What the number is used for

Questions

What is the full-load current of a 1,000 kVA transformer at 480 V?

1,203 A on the secondary.

What is the full-load current of a 75 kVA transformer at 208 V?

208 A.

Do the primary and secondary currents multiply to the same kVA?

Yes. 500 kVA at 13,800 V gives 20.9 A, and the same 500 kVA at 480 V gives 601 A. The power is equal on both sides, ignoring the small losses.

What is the full-load current of a 2,500 kVA transformer at 480 V?

2,500,000 / (1.732 × 480) = 3,007 A.

What is the full-load current on the 11 kV primary of a 1,000 kVA transformer?

1,000,000 / (1.732 × 11,000) = 52.5 A.

Sizing conductors and overcurrent protection from the chart

The full-load current on each side of the transformer sets the starting point for cable and device sizing, but the final size follows from the applicable standard.

NEC Article 450 — overcurrent protection

For transformers rated over 600 V, Article 450.3 sets the maximum overcurrent protection as a percentage of the rated current. The table values depend on whether protection is on the primary side, the secondary side, or both. Common limits:

Always verify against the current edition of the NEC for the exact row that applies to your voltage and situation.

Conductor sizing

A transformer secondary conductor is not a motor branch circuit. It does not get the automatic 125 % factor unless it feeds a continuous load. The conductor must be rated for the full-load current on that side. For a 500 kVA transformer at 480 V, the secondary full-load current is 601 A, which requires 1,000 kcmil copper or three sets of 250 kcmil in parallel, depending on conduit fill and ambient temperature.

Inrush and its effect on protection

On energising, the transformer draws magnetising inrush current. For distribution transformers this is typically 8–12 times the full-load current for the first few cycles, decaying over several seconds. The exact multiple depends on:

An 8× inrush on a 601 A transformer is 4,808 A for a fraction of a second. Fuses protecting the transformer must not blow on this. Standard transformer fuses (K-type or T-type current-limiting fuses) are selected with this in mind from the manufacturer’s curve or table. Relays use an inrush-restraint element or a time delay set to ride through the inrush period.

Taps and voltage adjustment

Distribution transformers often have no-load taps (±2.5 % and ±5 %) that allow the secondary voltage to be trimmed. If a transformer is set to its +5 % tap:

Transformer tap adjustments must be made with the transformer de-energised. Only load tap changers (LTCs), found on substation power transformers, allow on-load adjustment.

Typical transformer ratings for common loads

Load kVA Secondary V FLC (A)
Small commercial unit (lighting, HVAC) 75 208 208
Office floor or small retail 150 208 416
Medium commercial building 500 480 601
Large commercial building 1,000 480 1,203
Industrial facility, medium 1,500 480 1,804
Industrial facility, large 2,500 480 3,007
Data hall, medium 500 480 601
Data hall, large (utility entrance) 2,500 13,800 104.7

Single-phase transformers

Single-phase transformers use the formula I = kVA × 1000 / V, with no √3 factor. A 25 kVA single-phase unit at 240 V has a full-load current of 25,000 / 240 = 104.2 A. The kVA to amps calculator handles both phases.