Chart

Amps to kW Chart

Real power in kW for 5 to 200 A at 120 to 600 V, including 230 V and 400 V, single-phase and three-phase, with formulas and a worked example.

Updated 2026-11-19

ElectricalFree, no sign-upWorked examples

This chart converts a measured or rated current into real power in kW. Single-phase values use a power factor of 1.0. Three-phase values use 0.9, so scale them for your own power factor with the factor given below the tables.

Single-phase real power in kW, power factor 1.0
Amps120 V208 V230 V240 V
50.601.041.151.20
101.202.082.302.40
151.803.123.453.60
202.404.164.604.80
303.606.246.907.20
404.808.329.209.60
506.0010.4011.5012.00
607.2012.4813.8014.40
809.6016.6418.4019.20
10012.0020.8023.0024.00
15018.0031.2034.5036.00
20024.0041.6046.0048.00
Three-phase real power in kW, power factor 0.9
Amps208 V240 V400 V480 V600 V
51.621.873.123.744.68
103.243.746.247.489.35
154.865.619.3511.2214.03
206.487.4812.4714.9618.71
309.7311.2218.7122.4528.06
4012.9714.9624.9429.9337.41
5016.2118.7131.1837.4146.77
6019.4522.4537.4144.8956.12
8025.9429.9349.8859.8674.82
10032.4237.4162.3574.8293.53
15048.6456.1293.53112.24140.30
20064.8574.82124.71149.65187.06

The formulas

Single-phase: P = V × I × PF / 1000
Three-phase: P = √3 × VLL × I × PF / 1000

P is in kW, I is the line current in amps and VLL the line-to-line voltage. The same relations in reverse are on the kW to amps chart. For a value between rows or a different voltage, use the amps to watts calculator.

Worked example

A 40 A single-phase circuit at 240 V carries up to 40 × 240 = 9,600 W, or 9.6 kW at a power factor of 1.0. A three-phase feeder at 480 V and 60 A with a power factor of 0.9 carries 1.732 × 480 × 60 × 0.9 = 44.9 kW, matching the 60 A row.

To change the power factor, multiply the three-phase values by PF / 0.9. At a power factor of 0.8, the 60 A row becomes 44.9 × 0.8 / 0.9 = 39.9 kW.

Rated current is not available power

The numbers show what a given current represents, not what a circuit can safely supply. A 50 A breaker does not mean you can use 50 A for hours: continuous loads are limited to 80 % of the breaker rating under the NEC. The breaker amps to watts chart shows the usable power for each standard breaker. The conductor and its terminals also set a limit that this chart ignores.

Questions

How many kW is 100 amps?

At 240 V single-phase it is 24 kW. At 480 V three-phase and PF 0.9 it is 74.8 kW.

Is kW the same as kVA?

No. kVA is apparent power, V × I with no power factor. kW is the real part, kVA × PF. A load at PF 0.9 drawing 100 kVA is delivering 90 kW. Transformers and generators are rated in kVA for that reason.

Why does the three-phase formula have a square root of three?

The three line currents are 120° apart. Power from three balanced phases adds to √3 times the product of line voltage and line current.

What is the kW for a 200 A, 480 V three-phase circuit at PF 0.85?

200 × 1.732 × 480 × 0.85 / 1000 = 141.0 kW.

What current does a 50 kW three-phase load at 400 V and PF 0.9 draw?

50 × 1000 / (1.732 × 400 × 0.9) = 80.2 A.

Common load types and their typical power factors

The chart uses a fixed power factor of 0.9 for three-phase values, which suits most motor and resistive loads. Real loads vary:

Whenever the power factor differs from 0.9, scale the three-phase table values by (actual PF / 0.9).

Typical circuits and their continuous loads

Residential single-phase circuits (North America)

Circuit Volts Amps Continuous kW
Lighting/outlets 120 V 15 A 1.44
Lighting/outlets 120 V 20 A 1.92
Small appliance 120 V 20 A 1.92
Electric dryer 240 V 30 A 5.76
Range or oven 240 V 50 A 9.60
EV charger (Level 2) 240 V 48 A 9.22
Water heater 240 V 25 A 4.80

Continuous loads are limited to 80 % of the breaker rating. The figures above use that limit.

Industrial three-phase circuits (480 V)

Circuit Amps Continuous kW at PF 0.9
Small motor branch 15 A 11.2
General power panel feeder 60 A 44.9
Large motor branch 150 A 112.3
Main distribution panel 400 A 299.4
Transformer secondary 1,200 A 898.1

European and IEC single-phase circuits (230 V)

Circuit Amps Watts
Standard socket circuit 16 A 3,680
Heavy socket circuit 20 A 4,600
Cooker 32 A 7,360

European three-phase circuits (400 V line-to-line)

Circuit Amps kW at PF 0.9
Small motor, 400 V 10 A 6.2
Medium motor, 400 V 32 A 19.9
Sub-distribution panel 100 A 62.4
Main LV panel 400 A 249.4

Reading power from a clamp meter

A clamp meter measures current, not power. To get kW from a clamp reading:

  1. Note the voltage of the circuit.
  2. Note the number of phases.
  3. Estimate or measure the power factor (most modern clamp meters can measure PF directly).
  4. Apply the formula: single-phase P = V × I × PF / 1000; three-phase P = 1.732 × V × I × PF / 1000.

If the power factor is unknown, using 1.0 for single-phase resistive loads is accurate. For three-phase motor loads, 0.85 is a reasonable estimate at full load. The resulting kW is an approximation until PF is confirmed.

kW versus kVA — sizing equipment correctly

Transformers and generators are rated in kVA, not kW. The difference is the power factor:

This is why power factor correction on large sites pays back through smaller transformer and cable sizes, not just lower utility charges.

Effect of voltage on current for the same power

Lower supply voltage means more current for the same kW:

This is why high-voltage distribution reduces losses over long runs, and why 480 V is preferred over 240 V for industrial motor loads. The voltage drop calculator quantifies the loss for a specific cable run.