Calculator

Off-Grid Solar System Calculator

Size an off-grid solar system: number of panels, battery bank, inverter and charge controller from your daily load and site sun hours.

Updated 2026-11-23

Solar and EVFree, no sign-upFormula and worked example
Panels4 × 400 W (1.60 kW)
Battery463 Ah at 48 V (22.2 kWh)
Inverter2500 W continuous
Charge controller42 A minimum

An off-grid system is a chain: panels charge a battery through a controller, and an inverter turns the battery’s DC into AC for the load. Each link has a size, and all four depend on how much energy you use. This calculator sizes them together from nine inputs, each with a default you can change.

How it works

  1. Array. The panels must replace the day’s energy plus the loss in the battery and inverter. Array (W) = daily load / efficiency / (peak sun hours × performance ratio).
  2. Battery. Capacity (Ah) = daily load × days of autonomy / (DoD × V × efficiency), the same formula as the battery bank calculator.
  3. Inverter. The continuous rating is the peak simultaneous load plus a 25 % margin.
  4. Charge controller. Output current = installed array watts / battery voltage × 1.25, which is the current an MPPT controller can push into the battery at full sun, with margin.

Worked example

A cabin uses 5,000 Wh per day with a 2,000 W peak. It has 5 peak sun hours in its worst month, a performance ratio of 0.75, 400 W panels, a 48 V bank, 2 days of autonomy, 50 % DoD and a 0.9 efficiency.

Choosing the design month

An off-grid system fails in its worst month, not its average one. In the northern hemisphere, that is usually December. If you design from an annual average of 5 hours and winter gives 2, the batteries will go flat for weeks. Either design for winter, which means a larger and more expensive array that is oversized for summer, or add a generator and accept some fuel use in the weak months.

What to check next

Common mistakes

Questions

How many solar panels do I need to run a house off-grid?

It depends entirely on daily energy use and the worst-month sun. A home using 20 kWh per day needs around 6 kW of panels at 5 peak sun hours, and much more in a poor winter.

Is a generator cheaper than extra batteries?

Often, for the last few days a year. Compare the cost of the extra days of autonomy with the cost of a generator and its fuel.

Does the calculator assume MPPT or PWM?

The controller figure is a minimum output current. An MPPT controller is the common choice at these sizes.

Off-grid system component sizing table

Typical sizing relationships for a 48 V lithium off-grid system at different daily load levels:

Daily load Array (@ 5 PSH, PR 0.8) Battery (2 days, 80% DoD) Inverter Charge controller
1,000 Wh 250 W 65 Ah 1,000 W 10 A MPPT
3,000 Wh 750 W 196 Ah 2,000 W 20 A MPPT
5,000 Wh 1,250 W 326 Ah 3,000 W 30 A MPPT
10,000 Wh 2,500 W 651 Ah 5,000 W 60 A MPPT
20,000 Wh 5,000 W 1,302 Ah 8,000 W 100 A MPPT

MPPT current is array Wp / battery voltage. At 48 V: 1,250 W / 48 = 26 A, so the 30 A controller is correct.

Worked example: rural cabin

A cabin wants to run 500 W of LED lighting (4 h/day), a 100 W laptop (6 h/day), a 150 W fridge (running 8 h/day), and a 750 W water pump (1 h/day). Location: 4.5 peak sun hours.

Daily energy:

Array at PR 0.8: 4,550 / (4.5 × 0.8) = 1,264 W. Use 4 × 325 W panels = 1,300 W.

Battery at 2 days autonomy, 80% DoD, 48 V: (4,550 × 2) / (0.8 × 48) = 237 Ah. Use a 48 V, 250 Ah LiFePO4 bank.

Inverter: running load 1,500 W + pump start surge ~2,250 W = 3,750 W peak. Use a 4,000 W pure sine wave inverter.

Charge controller: 1,300 W / 48 V = 27 A. Use a 40 A MPPT controller.

Battery chemistry comparison

Chemistry Usable DoD Cycle life Weight Cost per kWh
Flooded lead-acid 50 % 300–500 cycles High Low
AGM 50–60 % 400–600 cycles High Medium
Gel 50–60 % 500–800 cycles High Medium
LiFePO4 80–90 % 2,000–5,000 cycles Low High

LiFePO4 delivers roughly 3–4× more usable energy over its lifetime despite the higher upfront cost, and it handles partial state of charge without sulfation. For off-grid systems used daily, it typically has a lower total cost of ownership over 10 years.

Panel orientation and seasonal variation

Latitude Optimal tilt Summer PSH Winter PSH Annual ratio
20° N 15–20° 6.0 5.0 0.83
35° N 30–35° 6.5 3.5 0.54
50° N 45–50° 6.0 2.0 0.33

At 50° N, winter delivers only a third of summer output. A system sized on annual average will fall 50–60 % short in December. Options: size for winter (overproduces in summer), install a backup generator, or accept grid use in winter.

More Q&As

How do I account for seasonal variation in my off-grid system?

Run the calculation using the worst-month PSH for your latitude, not the annual average. For the UK at 51° N that is about 1.5–2 PSH in December, which is roughly one-third of July. Sizing for the worst month means the array overproduces significantly in summer — plan to dump excess to a hot water element or accept it.

Can I mix panel brands or wattages in one array?

In a single string, all panels should be matched in voltage. In parallel strings, all strings should have equal voltage. Mixing wattages works within those constraints, but mismatched panels lose the benefit of higher-rated units because the lower panel limits the string.

How do I calculate the charge controller size for a 24 V system?

Divide total panel watts by system voltage: 1,000 W / 24 V = 41.7 A. Choose the next standard size up — a 50 A MPPT controller. Add 25 % for the array’s short-circuit current headroom.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.