The calculator answers one question: how many watts of panels are needed to produce a given amount of energy per day. It gives a planning estimate. A real design also checks the roof, the shading, the inverter and the local rules.
Formula
Panels = array (W) / panel rating (W), rounded up
Peak sun hours (PSH) are the number of hours per day at an irradiance of 1,000 W/m² that would deliver the same energy as the real day. A site with 5 kWh/m² of daily sunlight has 5 peak sun hours. Values of 3 to 6 are typical, depending on latitude, climate and season. Look up your site in a tool such as NREL’s PVWatts or the Global Solar Atlas and use the figure for the plane of your array, not for flat ground.
Performance ratio (PR) bundles every loss between the panel’s rated output and the energy you can use: heat, dust, wiring, mismatch, inverter conversion. About 0.75 is a common planning value for a well-built system, and a poor one can be lower.
Worked example
A household uses 30 kWh per day and has 5 peak sun hours. With a PR of 0.75:
Array = 30,000 / (5 × 0.75) = 8,000 W.
With 400 W panels that is 8,000 / 400 = 20 panels. The calculator rounds up, so a result of 7.8 panels becomes 8, and it reports the expected daily output of the rounded-up array.
Getting the inputs right
- Daily energy. Take a year of electricity bills, divide the total kWh by 365, and decide whether you want to cover all of it or only part. Off-grid and winter-limited systems need the worst month, not the average.
- Peak sun hours. An annual average hides the winter shortfall. If your goal is year-round cover, size from the weakest month, or accept that the grid or a generator fills the gap.
- Panel rating. The rating is measured under standard test conditions of 1,000 W/m² and 25 °C cell temperature. Real cells run hotter, and silicon loses roughly 0.3 to 0.4 % of its output per °C above 25 °C, which is part of the PR.
What this does not cover
Roof area is a practical limit: a 400 W panel is typically close to 2 m². Shading from chimneys, trees and neighbouring buildings can cut output far more than the PR assumes, especially when one shaded panel limits a string. Panels also lose a fraction of a percent of their output each year. Grid-connected systems also face export rules and inverter size limits that depend on the utility and the country.
Common mistakes
- Multiplying panel watts by 24 hours. Panels produce at full rating only around midday in clear conditions.
- Forgetting the PR. Using the nameplate overstates output by a quarter or more.
- Using a sunny-month figure for a winter-critical load.
Questions
How many panels do I need for a 2,000 kWh monthly bill?
That is about 66.7 kWh per day. At 5 peak sun hours and a PR of 0.75, the array is 17.8 kW, or 45 panels of 400 W.
How many kWh does a 5 kW array produce per day?
At 5 peak sun hours and a PR of 0.75, about 18.8 kWh.
Does the calculator size the inverter?
No. See the inverter size calculator, and for a battery system the off-grid calculator.
Solar panel sizing reference table
Array size and panel count for common residential and commercial scenarios (PR 0.75):
| Daily load | 3 PSH (cloudy climate) | 4 PSH (temperate) | 5 PSH (sunny) | 6 PSH (tropical) |
|---|---|---|---|---|
| 10 kWh | 4.4 kW (11×400W) | 3.3 kW (9×400W) | 2.7 kW (7×400W) | 2.2 kW (6×400W) |
| 20 kWh | 8.9 kW (23×400W) | 6.7 kW (17×400W) | 5.3 kW (14×400W) | 4.4 kW (11×400W) |
| 30 kWh | 13.3 kW (34×400W) | 10.0 kW (25×400W) | 8.0 kW (20×400W) | 6.7 kW (17×400W) |
| 50 kWh | 22.2 kW (56×400W) | 16.7 kW (42×400W) | 13.3 kW (34×400W) | 11.1 kW (28×400W) |
PSH values: UK/Germany average 2.5–3.5; US Northeast 3.5–4.5; US Southwest 5–6; Australia east coast 4.5–5.5.
Worked example: UK home with winter sizing
A UK household uses 10 kWh/day. The household wants to cover most of its consumption year-round. Worst-month PSH (December, tilted array at 35°): 1.8 PSH.
Annual average array: 10,000 / (4.2 × 0.75) = 3,175 W → 8 × 400 W panels.
Winter-sized array: 10,000 / (1.8 × 0.75) = 7,407 W → 19 × 400 W panels.
The winter-sized array overproduces by 2.3× in summer. Practical compromises:
- Fit the 8-panel (3.2 kW) array and accept grid top-up in winter.
- Fit the 19-panel array and export surplus in summer under a feed-in tariff.
- Fit 10–12 panels with a battery (stores afternoon surplus for evening use).
For a grid-tied UK system without export constraints, 10–14 panels is a typical design range that balances cost and self-consumption.
Panel technology comparison
| Technology | Typical efficiency | Temperature coefficient | Best for |
|---|---|---|---|
| Monocrystalline PERC | 20–23 % | −0.35 %/°C | Space-limited roofs |
| Polycrystalline | 16–18 % | −0.40 %/°C | Cost-sensitive installs |
| Bifacial mono | 21–24 % + rear | −0.35 %/°C | Ground mount, flat roofs |
| HJT (heterojunction) | 22–24 % | −0.26 %/°C | Hot climates |
| Thin-film (CdTe) | 16–19 % | −0.25 %/°C | Utility scale, partial shade |
HJT has the lowest temperature coefficient, so it outperforms silicon PERC in hot conditions. A PERC panel rated 400 W at 25 °C delivers about 384 W at 40 °C cell temperature (a common summer afternoon value), while HJT delivers about 393 W.
Roof area and shading
A 400 W panel is typically 1.72 m × 1.13 m ≈ 1.95 m². Required roof area ≈ panel count × 2 m² (allowing for spacing). A 20-panel, 8 kW array needs roughly 40 m² of unshaded south-facing roof.
Shading is the dominant loss factor not captured in PR. Even partial shading of one cell in a string without bypass diodes can cut the output of the entire string by 50–80 %. Microinverters or DC optimisers mitigate this — worth specifying on complex roofs or those with morning/afternoon shading.
More Q&As
Does panel orientation affect the calculation?
Yes. South-facing panels (in the northern hemisphere) at an angle equal to the site latitude capture maximum annual energy. East-west split roofs produce a flatter daily profile — useful for self-consumption — but 10–15 % less annual energy than a south-facing array. The PSH input should reflect the actual array orientation, not horizontal irradiance.
What is the difference between STC and NOCT ratings?
Standard Test Conditions (STC): 1,000 W/m², 25 °C cell temperature, AM1.5 spectrum. Normal Operating Cell Temperature (NOCT): 800 W/m², 20 °C ambient, 1 m/s wind. NOCT ratings are typically 10–15 % lower than STC and closer to real-world performance on a sunny afternoon. Performance ratios of 0.75–0.80 implicitly account for the gap.
How long do solar panels last, and how much do they degrade?
Modern silicon panels are warranted for 25–30 years at 80–87 % of original output. Degradation is typically 0.4–0.7 %/year, with a faster first-year drop (1–3 %) due to light-induced degradation (LID). After 25 years, an 0.5 %/year degradation leaves 88 % of original output.
Related calculators
Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.