Calculator

Motor Circuit Calculator

Look up NEC motor full-load current by horsepower and voltage, then size the conductor, overload and short-circuit device for a motor branch circuit.

Updated 2026-11-23

ElectricalFree, no sign-upFormula and worked example
Table full-load current14 A
Conductor ampacity at least17.5 A
Device maximum (250 %)35.0 A
Next standard size35 A

A motor circuit has three separate sizing jobs, and each one uses a different current. The conductor and the short-circuit device are sized from the full-load current in a code table. The overload protection is sized from the nameplate. Mixing these up is the most common error, so this calculator keeps them apart.

The three steps

Conductor ampacity ≥ 1.25 × table full-load current
Overload setting = 1.25 × nameplate current (1.15 × if the motor does not qualify)
Short-circuit device ≤ table percentage × table full-load current

Full-load current comes from Table 430.250 for three-phase motors and Table 430.248 for single-phase motors, by horsepower and voltage. The code directs you to use these tabulated values for conductor and short-circuit protection sizing, not the figure on the nameplate. The tables list the voltages 208, 230, 460 and 575 V for three-phase and 115 and 230 V for single-phase, which this calculator offers.

Conductors carry at least 125 % of the table current (430.22) for a single motor with continuous duty.

Overload protection uses the nameplate current: 125 % for a motor with a service factor of 1.15 or more or a marked temperature rise of 40 °C or less, and 115 % for other motors (430.32). The maximum setting is 140 % and 130 % respectively. If the motor still trips at those, check the load before raising anything.

The short-circuit and ground-fault device (430.52) has a maximum, which depends on its type: 250 % for an inverse-time circuit breaker, 175 % for a dual-element fuse, 300 % for a non-time-delay fuse and 800 % for an instantaneous-trip breaker. If the result is not a standard size, the next higher standard size is permitted.

Worked example

A 10 hp, 460 V, three-phase motor with a nameplate current of 13 A:

A 5 hp, 230 V motor has a table current of 15.2 A, so the conductor needs 19 A and the breaker maximum of 38 A rounds up to a 40 A standard size.

What this does not cover

Common mistakes

Questions

What is the full-load current of a 5 hp motor?

It depends on voltage and phase: 7.6 A at 460 V three-phase, 15.2 A at 230 V three-phase and 28 A at 230 V single-phase.

Why does the code use a table and not the nameplate?

Motors with the same horsepower can have different nameplate currents. The table gives a consistent basis for sizing circuits, while the overload device protects the actual motor.

What size breaker for a 3 hp motor?

At 230 V three-phase the table current is 9.6 A, so the inverse-time breaker maximum is 250 %, or 24 A, which is not a standard size. The next higher standard size is 25 A.

Does a motor need a separate overload device?

Generally yes. The short-circuit device protects the circuit and the overload device protects the motor.

Motor circuit sizing reference table — NEC 430 (three-phase, 460 V)

Horsepower Table FLC (460 V) Min conductor (A) Max inv-time breaker (A) Max dual-element fuse (A) Overload at 125% NP
1 hp 2.1 A 2.6 A 5.3 A (std: 6 A) 3.7 A (std: 4 A) 1.25 × NP
3 hp 4.8 A 6.0 A 12 A (std: 15 A) 8.4 A (std: 10 A) 1.25 × NP
5 hp 7.6 A 9.5 A 19 A (std: 20 A) 13.3 A (std: 15 A) 1.25 × NP
10 hp 14 A 17.5 A 35 A (std: 35 A) 24.5 A (std: 25 A) 1.25 × NP
15 hp 21 A 26.3 A 52.5 A (std: 60 A) 36.75 A (std: 40 A) 1.25 × NP
20 hp 27 A 33.8 A 67.5 A (std: 70 A) 47.3 A (std: 50 A) 1.25 × NP
25 hp 34 A 42.5 A 85 A (std: 90 A) 59.5 A (std: 60 A) 1.25 × NP
50 hp 65 A 81.3 A 162.5 A (std: 175 A) 113.75 A (std: 125 A) 1.25 × NP

NP = nameplate current. Overload uses nameplate, not table value. Inverse-time breaker maximum = 250% × table FLC. Next standard breaker size up is used when calculation is not a standard size (NEC 240.6(A)).

Worked example: 25 hp, 460 V, three-phase motor

Nameplate: 32 A, SF 1.15, 460 V, 3-phase, continuous duty.

Step 1 — table current (Table 430.250): 34 A.

Step 2 — conductor minimum: 1.25 × 34 = 42.5 A. Per Table 310.16, 8 AWG copper THHN at 75°C = 50 A, so 8 AWG minimum. If conduit run is long, check voltage drop with the voltage drop calculator.

Step 3 — overload protection (NEC 430.32): SF ≥ 1.15 → use 125% of nameplate: 1.25 × 32 = 40 A. Maximum allowed: 1.40 × 32 = 44.8 A, so a 40 A heater or relay in the motor starter.

Step 4 — inverse-time circuit breaker: 2.50 × 34 = 85 A. Next standard size = 90 A. Install a 90 A breaker.

Step 5 — dual-element time-delay fuse (alternative): 1.75 × 34 = 59.5 A → 60 A fuse.

Step 6 — disconnect means (NEC 430.110): rated not less than 115% of motor FLC: 1.15 × 34 = 39.1 A. A 60 A fusible disconnect or 60 A non-fused switch satisfies this.

NEC 430 motor circuit components

Component NEC article Sizing basis Key rule
Branch circuit conductors 430.22 125% × table FLC Minimum ampacity
Overload protection 430.32 125% × nameplate (115% for other motors) Protects motor from sustained overload
Short-circuit device 430.52 ≤ 250% × table FLC (inv-time breaker) Protects circuit on fault
Disconnecting means 430.102–110 ≥ 115% × table FLC Must be in sight of motor
Controller 430.83 Rated for HP and voltage Motor starter or contactor
Ground fault protection 430.96 Per 430.96 or equipment listing May be part of motor controller

Motor starting methods and their effect on circuit sizing

Starting method Starting current Circuit impact
Across-the-line (DOL) 600–700% FLC Highest starting current, largest short-circuit device
Star-delta ~200% FLC Reduced start, motor must be wired for star-delta
Soft starter Adjustable, typically 200–400% FLC Reduces breaker and conductor stress
Variable frequency drive (VFD) ≤ 150% FLC Lowest starting current; VFD input requires separate sizing

A VFD draws its input current from the supply at the VFD’s rated input, not from the motor’s starting characteristics. Size the branch circuit for the VFD’s rated input current per the VFD manufacturer’s data, not the motor table.

More Q&As

What if my breaker trips when the motor starts?

First check the breaker is a standard inverse-time type, not an instantaneous one. If it still trips, the code allows increasing the breaker to the next higher standard size, up to the 250% maximum (NEC 430.52(C)(1) Exception). For a motor that still trips at the maximum, switch to a dual-element time-delay fuse, which handles starting surges better than a breaker.

How do I size the wire for a motor fed through a variable frequency drive?

The VFD output wiring (VFD to motor) is sized from the motor’s table FLC × 1.25, same as a direct-connected motor. The VFD input wiring (panel to VFD) is sized from the VFD manufacturer’s rated input current, which may differ from the motor FLC because VFD efficiencies and input power factors vary.

Can a single circuit serve multiple motors?

Under NEC 430.53, several motors of 1 hp or less may share a branch circuit if each has its own overload and the circuit is protected by a device not exceeding the value allowed for the smallest motor on the circuit. For larger motors, separate circuits are almost always required. See 430.24 for the total circuit ampacity when more than one motor is connected.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.