A current transformer is rated to drive a stated load, its burden, with its stated accuracy. The load is the relay or meter plus the leads that connect it. Too much burden means the CT saturates at lower fault current than its nameplate suggests, and a relay that sees a distorted or reduced current can operate late or not at all. Checking the burden is a standard step in any protection design.
Formulas
Slead = Isn² × Rlead
S = Slead + Srelay
ALF′ = ALF × (Sn + Sct) / (S + Sct), with Sct = Isn² × Rct
L is the one-way lead length, doubled for the out-and-back loop, ρ the resistivity of copper and A the lead cross-section. Isn is the rated secondary current, 1 A or 5 A. Srelay is the relay’s burden at rated current, from its datasheet. Sn is the CT’s rated burden in VA, and ALF is the rated accuracy limit factor. Rct is the CT’s own secondary winding resistance, from the test report. ALF′ is the factor at the actual burden: a lighter burden than rated gives a higher effective accuracy limit, and a heavier burden gives a lower one.
Worked example
A 5 A CT rated 15 VA 5P20, with a secondary winding resistance of 0.2 Ω, feeds a relay burdening 1 VA through 20 m of 4 mm² copper, at 20 °C.
- Lead loop resistance: 2 × 20 × 0.017241 / 4 = 0.172 Ω.
- Lead burden: 5² × 0.172 = 4.31 VA.
- Total burden: 4.31 + 1 = 5.31 VA, which is 35 % of the rated 15 VA.
- Sct = 25 × 0.2 = 5 VA.
- ALF′ = 20 × (15 + 5) / (5.31 + 5) = 38.8.
The CT is comfortably within its rating, and its effective accuracy limit is well above 20.
Why 1 A secondaries exist
Lead burden scales with the square of the secondary current. The same 0.172 Ω loop burdens a 5 A CT with 4.31 VA but a 1 A CT with only 0.17 VA. For long runs, as between a switchyard and a control room, a 1 A secondary can be the difference between a CT that works and one that doesn’t. A 200 m run of 2.5 mm² on a 5 A CT has 2.76 Ω of loop resistance, or 69 VA of lead burden alone, which far exceeds a 15 VA CT. On a 1 A CT the same cable is 2.8 VA.
Reading the CT designation
A designation such as 15 VA 5P20 reads as follows: 15 VA rated burden, protection class 5P, with a composite error of no more than 5 % at 20 times the rated current. Standard rated burdens under IEC 61869-2 include 2.5, 5, 10, 15 and 30 VA. For high-speed schemes such as differential and distance protection, the manufacturer may require a class PX or TPY CT specified by its knee-point voltage, and the burden check is then done against that voltage.
Limits of this check
- It is a burden check, not a saturation study. Whether the CT saturates for a given fault depends on the fault current, the X/R ratio, the remanent flux and the relay’s requirement. The relay manufacturer’s guidance sets the required knee point.
- Connection matters. The lead loop resistance used here is the full out-and-back path, which suits a single-phase or earth-fault burden. In a three-phase star connection the burden seen by each CT on a balanced fault is lower, and the relay manual states the factors.
- Temperature. Copper resistance rises with temperature, so use a realistic lead temperature, not the 20 °C default, if the run is outdoors in a hot climate.
Common mistakes
- Forgetting the lead loop is twice the length.
- Ignoring the CT’s own resistance.
- Adding burdens in ohms and VA as if they were the same unit.
Questions
What is a typical relay burden?
Modern numerical relays burden the CT at well under 1 VA at rated current. Older electromechanical relays could draw several VA.
Can I connect two relays to one CT?
Yes, in series, and their burdens add. Check the total, with the leads, against the rated burden.
What happens if the burden is too high?
The CT saturates earlier, its output distorts and the relay may under-read the fault current.
CT burden reference table
Lead burden (VA) for common lead lengths and cross-sections, 5 A secondary (loop resistance = 2 × ρ × L / A, burden = 5² × R):
| Lead length | 1.5 mm² Cu | 2.5 mm² Cu | 4.0 mm² Cu | 6.0 mm² Cu |
|---|---|---|---|---|
| 10 m loop | 5.75 VA | 3.45 VA | 2.16 VA | 1.44 VA |
| 20 m loop | 11.49 VA | 6.90 VA | 4.31 VA | 2.87 VA |
| 30 m loop | 17.24 VA | 10.34 VA | 6.47 VA | 4.31 VA |
| 50 m loop | 28.74 VA | 17.24 VA | 10.78 VA | 7.18 VA |
| 100 m loop | 57.47 VA | 34.48 VA | 21.55 VA | 14.37 VA |
For a 1 A secondary, divide all VA values by 25. The 1 A secondary dramatically reduces lead burden: 20 m loop on 2.5 mm² goes from 6.90 VA to 0.28 VA.
Worked example: selecting CT class for a distance relay
A 11 kV feeder has a 300/5 A CT installed in a switchroom. The distance relay is 50 m away, connected by 2.5 mm² copper pilot cable. Relay burden: 0.5 VA. CT nameplate: 15 VA 5P20, Rct = 0.5 Ω.
Step 1 — lead burden: Loop resistance = 2 × 50 × 0.017241 / 2.5 = 0.690 Ω. Lead burden = 25 × 0.690 = 17.25 VA.
Step 2 — total burden: S = 17.25 + 0.5 = 17.75 VA. This exceeds the rated 15 VA.
Step 3 — corrected ALF: Sct = 25 × 0.5 = 12.5 VA. ALF′ = 20 × (15 + 12.5) / (17.75 + 12.5) = 20 × 27.5 / 30.25 = 18.2.
The CT still functions at ALF 18.2, but to meet the full ALF 20 at 50 m, options are: (a) upgrade to 4.0 mm² cable (burden drops to 10.78 + 0.5 = 11.28 VA → ALF′ = 22.6), or (b) specify a 30 VA rated CT.
1 A vs 5 A secondary: when to choose each
| Factor | 5 A secondary | 1 A secondary |
|---|---|---|
| Short leads (< 10 m) | Preferred | No advantage |
| Long leads (> 30 m) | High burden risk | 25× lower lead burden |
| Local metering | Standard | Less common |
| Remote metering (100+ m) | Pilot upgrade needed | Standard choice |
| Pilot cable cost saving | — | Smaller cable acceptable |
| Instrument output | Standard relays | Relays must specify 1 A |
The rule of thumb: use 1 A secondaries when the CT-to-relay distance exceeds 30 m in a 5 A scheme, or when the pilot cable cross-section would need to exceed 4 mm² to stay within the CT’s burden.
IEC CT class designations
| Designation | Class | Composite error | Typical use |
|---|---|---|---|
| 5P10 | Protection | ≤ 5% at 10× rated | IDMT overcurrent relays |
| 5P20 | Protection | ≤ 5% at 20× rated | Feeder and transformer protection |
| 10P20 | Protection | ≤ 10% at 20× rated | Earth fault protection only |
| PX / TPX | Special | Defined by Vk | Differential, distance protection |
| 0.5 | Metering | ≤ 0.5% | Revenue metering |
| 0.2 | Metering | ≤ 0.2% | High-accuracy metering |
For distance and differential protection, the relay manufacturer specifies a minimum knee-point voltage (Vk) or saturation voltage. Standard 5P class CTs may not meet this requirement: check the relay’s CT requirement document before specifying the CT.
More Q&As
How do I measure a CT’s secondary winding resistance in the field?
Inject a small DC current (≤ 100 mA) through the secondary terminals with the primary open-circuited. Measure the terminal voltage. Rct = V/I. Never inject current with the primary closed — the primary will see a very high voltage.
What is remanent flux, and why does it matter for CT saturation?
Remanent flux is residual magnetisation left in the CT core after a fault is cleared by the breaker. If a subsequent fault occurs before the core demagnetises, the CT reaches saturation much earlier — sometimes on the first cycle. High-remanence cores (class P) can have 80% residual flux. TPX and TPY classes define limits on remanent flux for high-speed protection schemes.
Can a CT be used at a lower secondary current than rated?
Yes. A CT rated 300/5 A used on a 100 A primary circuit operates the secondary at 1.67 A rather than 5 A. The burden and accuracy are still governed by the nameplate, but the actual secondary current and burden are proportionally lower. The CT operates well within its rating.
Related calculators
Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.