Calculator

CT Burden Calculator

Check a current transformer's connected burden from lead length, lead size and relay burden, and the resulting effective accuracy limit factor.

Updated 2026-11-23

Protection and MVFree, no sign-upFormula and worked example
Lead loop resistance0.172 Ω
Lead burden4.31 VA
Total connected burden5.31 VA
Share of rated burden35 %
Effective ALF38.8
Within rated burdenYes

A current transformer is rated to drive a stated load, its burden, with its stated accuracy. The load is the relay or meter plus the leads that connect it. Too much burden means the CT saturates at lower fault current than its nameplate suggests, and a relay that sees a distorted or reduced current can operate late or not at all. Checking the burden is a standard step in any protection design.

Formulas

Rlead = 2 × ρ × L / A
Slead = Isn² × Rlead
S = Slead + Srelay
ALF′ = ALF × (Sn + Sct) / (S + Sct), with Sct = Isn² × Rct

L is the one-way lead length, doubled for the out-and-back loop, ρ the resistivity of copper and A the lead cross-section. Isn is the rated secondary current, 1 A or 5 A. Srelay is the relay’s burden at rated current, from its datasheet. Sn is the CT’s rated burden in VA, and ALF is the rated accuracy limit factor. Rct is the CT’s own secondary winding resistance, from the test report. ALF′ is the factor at the actual burden: a lighter burden than rated gives a higher effective accuracy limit, and a heavier burden gives a lower one.

Worked example

A 5 A CT rated 15 VA 5P20, with a secondary winding resistance of 0.2 Ω, feeds a relay burdening 1 VA through 20 m of 4 mm² copper, at 20 °C.

The CT is comfortably within its rating, and its effective accuracy limit is well above 20.

Why 1 A secondaries exist

Lead burden scales with the square of the secondary current. The same 0.172 Ω loop burdens a 5 A CT with 4.31 VA but a 1 A CT with only 0.17 VA. For long runs, as between a switchyard and a control room, a 1 A secondary can be the difference between a CT that works and one that doesn’t. A 200 m run of 2.5 mm² on a 5 A CT has 2.76 Ω of loop resistance, or 69 VA of lead burden alone, which far exceeds a 15 VA CT. On a 1 A CT the same cable is 2.8 VA.

Reading the CT designation

A designation such as 15 VA 5P20 reads as follows: 15 VA rated burden, protection class 5P, with a composite error of no more than 5 % at 20 times the rated current. Standard rated burdens under IEC 61869-2 include 2.5, 5, 10, 15 and 30 VA. For high-speed schemes such as differential and distance protection, the manufacturer may require a class PX or TPY CT specified by its knee-point voltage, and the burden check is then done against that voltage.

Limits of this check

Common mistakes

Questions

What is a typical relay burden?

Modern numerical relays burden the CT at well under 1 VA at rated current. Older electromechanical relays could draw several VA.

Can I connect two relays to one CT?

Yes, in series, and their burdens add. Check the total, with the leads, against the rated burden.

What happens if the burden is too high?

The CT saturates earlier, its output distorts and the relay may under-read the fault current.

CT burden reference table

Lead burden (VA) for common lead lengths and cross-sections, 5 A secondary (loop resistance = 2 × ρ × L / A, burden = 5² × R):

Lead length 1.5 mm² Cu 2.5 mm² Cu 4.0 mm² Cu 6.0 mm² Cu
10 m loop 5.75 VA 3.45 VA 2.16 VA 1.44 VA
20 m loop 11.49 VA 6.90 VA 4.31 VA 2.87 VA
30 m loop 17.24 VA 10.34 VA 6.47 VA 4.31 VA
50 m loop 28.74 VA 17.24 VA 10.78 VA 7.18 VA
100 m loop 57.47 VA 34.48 VA 21.55 VA 14.37 VA

For a 1 A secondary, divide all VA values by 25. The 1 A secondary dramatically reduces lead burden: 20 m loop on 2.5 mm² goes from 6.90 VA to 0.28 VA.

Worked example: selecting CT class for a distance relay

A 11 kV feeder has a 300/5 A CT installed in a switchroom. The distance relay is 50 m away, connected by 2.5 mm² copper pilot cable. Relay burden: 0.5 VA. CT nameplate: 15 VA 5P20, Rct = 0.5 Ω.

Step 1 — lead burden: Loop resistance = 2 × 50 × 0.017241 / 2.5 = 0.690 Ω. Lead burden = 25 × 0.690 = 17.25 VA.

Step 2 — total burden: S = 17.25 + 0.5 = 17.75 VA. This exceeds the rated 15 VA.

Step 3 — corrected ALF: Sct = 25 × 0.5 = 12.5 VA. ALF′ = 20 × (15 + 12.5) / (17.75 + 12.5) = 20 × 27.5 / 30.25 = 18.2.

The CT still functions at ALF 18.2, but to meet the full ALF 20 at 50 m, options are: (a) upgrade to 4.0 mm² cable (burden drops to 10.78 + 0.5 = 11.28 VA → ALF′ = 22.6), or (b) specify a 30 VA rated CT.

1 A vs 5 A secondary: when to choose each

Factor 5 A secondary 1 A secondary
Short leads (< 10 m) Preferred No advantage
Long leads (> 30 m) High burden risk 25× lower lead burden
Local metering Standard Less common
Remote metering (100+ m) Pilot upgrade needed Standard choice
Pilot cable cost saving — Smaller cable acceptable
Instrument output Standard relays Relays must specify 1 A

The rule of thumb: use 1 A secondaries when the CT-to-relay distance exceeds 30 m in a 5 A scheme, or when the pilot cable cross-section would need to exceed 4 mm² to stay within the CT’s burden.

IEC CT class designations

Designation Class Composite error Typical use
5P10 Protection ≤ 5% at 10× rated IDMT overcurrent relays
5P20 Protection ≤ 5% at 20× rated Feeder and transformer protection
10P20 Protection ≤ 10% at 20× rated Earth fault protection only
PX / TPX Special Defined by Vk Differential, distance protection
0.5 Metering ≤ 0.5% Revenue metering
0.2 Metering ≤ 0.2% High-accuracy metering

For distance and differential protection, the relay manufacturer specifies a minimum knee-point voltage (Vk) or saturation voltage. Standard 5P class CTs may not meet this requirement: check the relay’s CT requirement document before specifying the CT.

More Q&As

How do I measure a CT’s secondary winding resistance in the field?

Inject a small DC current (≤ 100 mA) through the secondary terminals with the primary open-circuited. Measure the terminal voltage. Rct = V/I. Never inject current with the primary closed — the primary will see a very high voltage.

What is remanent flux, and why does it matter for CT saturation?

Remanent flux is residual magnetisation left in the CT core after a fault is cleared by the breaker. If a subsequent fault occurs before the core demagnetises, the CT reaches saturation much earlier — sometimes on the first cycle. High-remanence cores (class P) can have 80% residual flux. TPX and TPY classes define limits on remanent flux for high-speed protection schemes.

Can a CT be used at a lower secondary current than rated?

Yes. A CT rated 300/5 A used on a 100 A primary circuit operates the secondary at 1.67 A rather than 5 A. The burden and accuracy are still governed by the nameplate, but the actual secondary current and burden are proportionally lower. The CT operates well within its rating.

Related calculators

Found a wrong value or formula? Report an error. Confirmed fixes are listed on the corrections log.